InDelta Connections For Delta connected motors, the SoftStart can be connected inside the delta windings.
This connection method is shown in Figure 2-2.
Figure 2-2 InDelta SoftStart Connections
L1 L2 L3
Alternate *
Fuse
Connection
Note 1
L1 L2 L3
L1 L2 L3
* Circuit
Breaker
Earth
* Optional components not provided with control.
Note 3, 9
Baldor
Digital
SoftStart
Note 1
Notes:
1. See Protective Devices described previously in this section.
2. Use same gauge wire for Earth ground as is used for L1, L2 and L3.
3. Metal conduit should be used. Connect conduits so the use of a Reactor or RC
Device does not interrupt EMI/RFI shielding.
4. Derating factor for softstart is 57%.
5. Parameter P6 Firing Mode must be set to 1.
6. X1 and X2 control terminal power must be present or the logic circuits will not work.
Either 115VAC or 230VAC can be used. Be sure the 115/230VAC switch (Control
Voltage Selector Switch) is set to the proper voltage before you apply power.
7. The X1 and X2 control voltage input has different VA ratings depending on enclosure
size, see Table 2-3.
8. For reversing operation, L1 and L2 should be switched. Reversing any two of the
three input phases will reverse the motor rotation.
9. To protect the control, be sure to add MOV protection. Refer to Appendix D for
additional information.
Note 2
See Recommended Tightening
Torques in Table 2-4.
* AC Motor
T1 T2 T3
T3
T1
T2
G
T5
T6
T4
InDelta connections for correct motor rotation
SoftStart
Terminal
T1
T2
T3
L1
L2
L3
Motor
Terminal
T3
T1
T2
T5
T6
T4
115/230VAC
Note 6, 7
X1
X2
Note 8
Fan Connections Size 3 and 4 only Size 1 and 2 controls do not have fan connections. For Size 3 controls make
the fan connections as shown in Figure 2-3.The Fan and Control voltages must be the
same (both must be 115VAC or both must be 230VAC). 150VA (minimum) required.
Figure 2-3 Fan Connections
230V Connections
(150VA minimum) X1 X2
115V Connections
X1 X2