The current limit may be adjusted as follows:
A. Connect an AC RMS ammeter in series with one motor phase.
B. Set the CL Trimpot fully counterclockwise.
C. Adjust the speed setting to 30%.
D. Lock the motor shaft and adjust the CL Trimpot to 160% of the motor nameplate
rated current.
8 DRIVE OPERATION
8.1 START-UP PROCEDURE: After the drive has been properly setup (jumpers and
trimpots set to the desired positions) and wiring completed, the start-up procedure can
begin.
WARNING! MAKE SURE THAT THE POTENTIOMETER IS SET FULLY
COUNTERCLOCKWISE PRIOR TO APPLYING POWER. IF THIS IS NOT DONE, THE
MOTOR WILL RUN AT THE SPEED SETTING AT POWER UP. THIS MAY CAUSE BODILY
INJURY IF ONE IS IN CLOSE PROXIMITY OF MOVING PARTS.
To start the drive, set the On/Off AC Line Switch to the “ON” position. If the AC power
has been properly brought to the drive, the Pilot Light will illuminate. If the optional
Forward-Stop-Reverse Switch has been installed, set it to the “FWD” or “REV” position.
The motor will begin to accelerate to the set speed. The PC board mounted “ST” and
“OL” LED’s will indicate the drive status, as described in Section 9.3 and 9.4 on page 25.
8.2 RESTARTING THE DRIVE AFTER A FAULT HAS BEEN CLEARED: The drive
monitors four faults (Undervoltage, Overvoltage, Short Circuit (at the motor (phase-to-
phase)), and Overload). The PC board mounted “ST” and “OL” LED’s will indicate the
drive status, as described in Section 9.3 and Section 9.4, on page 25. Also see Section
6.3, on page 19, for Automatic or Manual Start and Reset selection with Jumper J3. In
addition, Section 10.2 on page 26.
WARNING! THE DRIVE WILL AUTOMATICALLY RESTART AFTER FAULT
HAS CLEARED. IF AN I
2
T OR SHORT CIRCUIT FAULT OCCURS, THE DRIVE MUST BE
RESTARTED BY SETTING THE ON/OFF AC LINE SWITCH TO THE “OFF” POSITION
FOR A MINIMUM OF 5 SECONDS.
8.2.1 Drive Set for Automatic Start and Reset (Factory Setting): The drive will
automatically restart after an Undervoltage or Overvoltage Fault has cleared. For
an I
2
t Fault, be sure the fault has been cleared before restarting the drive. Check
the motor current with an AC RMS responding ammeter. Also, the CL setting
may be set too low. See Section 7.6, on page 23. For an I
2
t or Short Circuit
Fault, the drive must be restarted by setting the On/Off AC Line Switch to the
“OFF” position for a minimum of 5 seconds.