User Guide
Section 4
Parameter Index
Parameter Index 4-1MN850
Menu Descriptions
Basic Menu
Block Title Parameter Description
Basic Starting Keypad – Allows motor starting and stopping by pressing Start/Stop key on keypad.
Remote – Allows motor starting and stopping by applying or removing 115VAC at
terminals S0 and S1 of the control board.
Start Pedestal Start Pedestal Voltage – end of stop smoothing and beginning of low voltage ramp to
zero volts (if low voltage ramp is active).
Start Time Number of seconds after the 3 cycle power–up to full motor voltage.
Stop Pedestal Stop Pedestal Voltage is the percentage of line voltage applied to the motor after a stop
command.
Stop Time Time in seconds after a stop command to ramp down the motor voltage (Stop Time 1 or
2). Stop Time 1 with low voltage ramp active. Stop Time 2 with no low voltage ramp.
Current Limit Percentage of running current (P24 and P25). Adjustable from 100 – 800%.
Power on
Parameter
Resets all parameter values to the values at the most recent power up. Display blinks
twice to confirm reset is complete.
Protection Full – provides shorted SCR protection during start and run, single phase protection
during start, optimizing not selected.
Full + Optimise – provides shorted SCR protection during start and run, single phase
protection during start, optimizing is selected.
Start + Bypass – provides shorted SCR protection during start, single phase protection
during start, optimizing not selected and no single phase protection during run.
This mode must be used with top of ramp bypass contactor.
Phase Loss only – shorted SCR protection during start and run is disabled, single phase
protection during start, optimizing not selected.
This mode is recommended when input power noise frequently causes nuisance trips.
Applications Menu
Block Title Parameter Description
Applications Settings Display starting method, either Keypad or Remote. Also displays operating mode
(Optimizing or Full Voltage).
Default (Keypad) Sets starting and stopping mode to keypad, resets control and restores all parameters to
factory preset values.
Small Pump Uses preset parameter values for typical small centrifugal pump. (P11, P12, P16, P17,
P30 and P31 values).
Large Pump Uses preset parameter values for typical large centrifugal pump. (P11, P12, P16, P17,
P30 and P31 values).
Conveyor Uses preset parameter values for typical conveyor. (P11, P12, P16, P17, P30 and P31
values).
Low Inertia Fan Uses preset parameter values for Low Inertia Fan. (P11, P12, P16, P17, P30 and P31
values).
High Inertia Fan Uses preset parameter values for High Inertia Fan. (P11, P12, P16, P17, P30 and P31
values).
Reciprocating 
Compressor
Uses preset parameter values for Reciprocating Compressor. (P11, P12, P16, P17, P30
and P31 values).
Screw Compressor Uses preset parameter values for Screw Compressor.  (P11, P12, P16, P17, P30 and
P31 values).
Rotary Compressor Uses preset parameter values for Rotary Compressor.  (P11, P12, P16, P17, P30 and
P31 values).