5-2 Troubleshooting MN850
Table 5-2 Troubleshooting Guide
INDICATION CORRECTIVE ACTION
Unit fails to start LED’s on control card are OFF and no error messages displayed:
1. Verify that 115VAC is present at X1 and X2 terminals.
2. Verify that 9VAC is present at terminal J2 (see Section 2 cover removal).
Green power LED is ON and no error messages displayed:
1. Control board or other component may be defective. Contact Baldor.
Unit trips during
start
1. Check parameter 73 (last trip) error code and isolate source of problem (see Table 5-1).
2. Verify that all three phases of AC input power and motor power are present (no missing phases).
3. If input contactor is used, verify AC input power is present at L1, L2 and L3 before the contactor delay time
is complete. If the SCRs fire before AC power is present, the Phase Loss message is displayed and
unit will trip.
4. Verify all connections at the SCR gate connections. (Resistance check: with all power removed, the
resistance between adjacent Red & Yellow wires at the control card connections can be checked.
Between pins 12, 34, 58 etc. the resistance should be between 10 50 ohms ±20%.
5. Verify there are no power factor correction capacitors on the output. Power factor correction capacitors may
only be connected on the line side of the control and must be switched out during starting.
6. Verify SCR are not shorted (error display Motor SCR Loss). (Resistance check: with all power removed,
the resistance can be checked between adjacent Red to Red wires at the control connections. Between
pins 14 (L3 & T3), 58 (L2 & T2) and 912 (L1 & T1) the resistance must be greater than 500k ohms.
7. If the “Shearpin” or “Overload” messages are displayed, verify that the softstart control is correctly sized.
8. If the Too Hot message is displayed, verify the thermal switch connection (or jumper is installed) at J4.
9. If the Sensing Signal or SCR Signal messages are displayed, problem can be excess noise or failure on
another circuit board. Contact Baldor.
10. Verify that the motor is less than 328ft.(100m) from the softstart control.
Bad start then unit
trips
1. Check parameter 73 (last trip) error code and isolate source of problem (see Table 5-1).
2. Verify that AC input power and motor power wires are not reversed. (The motor will give an initial kick then
start very roughly.)
3. Verify all connections at the SCR gate connections. (Resistance check: with all power removed, the
resistance between adjacent Red & Yellow wires at the control card connections can be checked.
Between pins 12, 34, 58 etc. the resistance should be between 10 50 ohms ±20%.
4. Verify there are no power factor correction capacitors on the output. Power factor correction capacitors may
only be connected on the line side of the control and must be switched out during starting.
5. Verify SCR are not shorted (error display Motor SCR Loss). (Resistance check: with all power removed,
the resistance can be checked between adjacent Red to Red wires at the control connections. Between
pins 14 (L1 & T1), 58 (L2 & T2) and 912 (L3 & T3) the resistance must be greater than 500k ohms.
6. Verify that the motor is less than 328ft.(100m) from the softstart control.
SCR’s short on
first start–up
1. Verify there are no power factor correction capacitors on the output. Power factor correction capacitors may
only be connected on the line side of the control and must be switched out during starting.
2. Verify that the softstart control is correctly sized. Verify the Rated Current, Overload Trip level, and trip
delay are correct for the application.
3. Verify that the motor is less than 328ft.(100m) from the softstart control. Also, verify the motor and motor
leads are good.
Unit trips during
ramp–up
1. Check parameter 73 (last trip) error code and isolate source of problem (see Table 5-1).
2. Verify that all three phases of AC input power and motor power are present (no missing phases).
Check for blown fuse if Phase Loss message is displayed.
3. Verify that the softstart control is correctly sized. Verify the Rated Current, Overload Trip level, and trip
delay are correct for the application.
4. If the Too Hot message is displayed, verify the thermal switch connection (or jumper is installed) at J4.