User Guide
Appendix B
Parameter Values
Applications B-1MN850
Version 5MC (4/2/01)   Read Only Parameter Values
Title P# Parameter Adjustable Range Factory User Setting
Parameter P0 Dummy Parameter 0–255 0
P1 Station Number 1–99 1
P2 Country 1–255 44 (England)
P3 Software Type Factory Set Read Only
P4 Software Version Factory Set Read Only
Password P5 Password Value 0–255 0
Advanced P6 Firing Mode 0–3 0
Basic P7 Protection Mode 0–192 192 (Full + Optimize)
Parameters P8 Status 1 0–255 1 (bit 00000001)
P9 Status 2 0–99 0 (bit 00000000)
P10 Status 3 0–255 0 (bit 0000000)
Basic P11 Start Pedestal 10–60% 20 (% of line volts)
P12 Start Time 1–255 seconds 5 (seconds)
Advanced P13 Kick Pedestal 60–90% 75 (% of Line)
P14 Kick Time 10–40 cycles 25 Cycles
P15 Dwell Time 1–255 seconds 5 seconds
Basic P16 Stop Pedestal 10–60% 10 (% of Line)
P17 Stop Time 0–255 seconds 0 seconds
Auto Features P18 Auto Config. 0–255 6 (bit 00000110)
Advanced P19 Optimise Rate 4–30 5 (for unstable load)
Parameters P20 Reference PF (Power Factor) 0–147 degrees 146.7626 degrees
P21 Present PF (Power Factor) 0–147 degrees 146.7626 degrees
P22 Delay Angle (SCR OFF time) 0–147 degrees 146.7626 degrees
P23 Maximum Optimizing Delay 17–147 degrees 57.55396 degrees
P24 Rated Current (High Byte –Hundreds) Factory Set Factory Set
P25 Rated Current (Low Byte – Units) Factory Set Factory Set
P26 Running Current Amps 0–255 Amps 0 Amps
P27 Peak Start Current (measured at last start) 0–255 Amps 0 Amps
Advanced Current P28 Low Current Level (undercurrent trip) 100–800% of running
Amps (P24 & P25)
9.375% of running
Amps
P29 Low Current Time (delay before trip) 5–255 seconds 50 seconds
P30 Current Limit Level (scaling = 0.03125) 1–7.96875 (x Ie) Amps 350% of running
Amps
P31 Current Limit Time (delay before trip) 5–255 seconds 30 seconds
P32 Shearpin Level (undercurrent trip) 1–5 (x Ie) Amps 3.125 x Ie Amps
P33 Shearpin Time (delay before trip) 5–255 cycles 100 cycles
P34 Overload Level (SCR protection) 0.59–2 (x Ie) Amps 1.09375 x Ie Amps
P35 Overload Delay (delay before trip) 10–140 140
Note: (x Ie) means “Times the rated current of the control (P24 and P25 values).”