User Guide

Voltage Surge Protection D-3MN850
Figure D-3 Delta Configurations
Ungrounded
L1
L1
L2
L3
L2 L3 T1 T2 T3
Control
Enclosure
Symbol
Corner or CenterTap
Grounded
L1
L1
L2
L3
L2 L3 T1 T2 T3
Control
Enclosure
Symbol
Do not ground MOV. Cut off green wire and insulate (cap off) with wire nut.
Do not ground MOV. Cut off green wire and insulate (cap off) with wire nut.
MOV
MOV
Table D-1 Baldor MOV Specifications
Catalog # MOV505L MOV620EL
Line Voltage Volts 480 575
Energy Joules 260 300
Peak Current Amps 6500 6500
Clamping Voltage Volts 1300 1580