User manual

Modbus RTU 25MN744
Parameter Support Continued
Read Parameter Dynamic Fields
(Sub-Code 5)
This PDU is directed towards the active parameter table only. It is used to read the current settings for fields
within a parameter that are subject to change.
Request PDU
Byte 1
Byte 2 Byte 3 Byte 4
Function Code (67) Sub-Code (5) Parameter Number
Where,
Byte 1: Parameter Support function code 67 (0x43)
Byte 2: Parameter dynamic fields Sub-Code
Byte 3-4: 16-Bit Parameter Number (PN)
Response PDU:
Byte 1
Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Byte 9 Byte 10 Byte 11 Byte 12
Function Code (67) Sub-Code (5) Parameter Number Maximum Value Default Value (Factory Setting)
Byte 13 Byte 14 Byte 15 Byte 16 Byte 17 Byte 18 Byte 19 Byte 20 Byte 21 Byte 22 Byte 23
Current Value Minimum Value Units Data Type Resolution
Where,
Bytes 5-8: Maximum parameter value (Data in high to low byte order)
Bytes 9-12: Parameter default value (Data in high to low byte order)
Bytes 13-16: Parameter current value (Data in high to low byte order)
Bytes 17-20: Parameter minimum value (Data in high to low byte order)
Byte 21: Units as defined in the configuration PDU
Byte 22: Data type as defined in the configuration PDU
Byte 23: Digits to the right of the decimal point (resolution)
Read Parameter Fields from Parameter Table (Sub-Code 6)
This PDU allows access to parameter fields as they exist within the parameter tables. It is used to read certain
fields as defined below within a parameter.
Request PDU
Byte 1
Byte 2 Byte 3 Byte 4 Byte 5
Function Code (67) Sub-Code (6) Table Index Parameter Number
Where,
Byte 1: Parameter Support function code 67 (0x43)
Byte 2: Parameter dynamic fields Sub-Code
Byte 3: Parameter table index (0-3)
Byte 4-5: 16-Bit Parameter Number (PN)
Response PDU:
Byte 1
Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Byte 9 Byte 10 Byte 11 Byte 12 Byte 13
Function Code (67) Sub-Code (6) Table Index Parameter Number Maximum Value Default Value (Factory Setting)
Byte 14 Byte 15 Byte 16 Byte 17 Byte 18 Byte 19 Byte 20 Byte 21 Byte 22 Byte 23 Byte 24
Current Value Minimum Value Units Data Type Resolution
Where,
Bytes 6-9: Maximum parameter value (Data in high to low byte order)
Bytes 10-13: Parameter default value (Data in high to low byte order)
Bytes 14-17: Parameter current value (Data in high to low byte order)
Bytes 18-21: Parameter minimum value (Data in high to low byte order)
Byte 22: Units as defined in the configuration PDU
Byte 23: Data type as defined in the configuration PDU
Byte 24: Digits to the right of the decimal point (resolution)