User Guide
8-2 
AC 
OUTPUT MEASURING 
4 
To 
AC 
receptacle 
Fig. 
8-8 
Measurement is executed with  the circuit as shown in Fig. 
8-8. 
An  electric heater or an  incandescent 
lamp with a power factor of 
1.0 
is suitable 
as 
a load for the generator. When the AC output measured at 
the rated load and rated speed 
is 
confirmed to be within the voltage  range specified in the table  below, 
the AC output 
is 
normal. 
I 
Rated voltage 
I 
120v 
I 
Voltage range 
1 
17-1 
30V 
Table 
8-2 
8-3 
DC 
OUTPUT MEASURING 
I 
To 
DC 
Terminal 
-l 
I 
P 
Fig. 
8-9 
Measurement of DC output 
is 
executed with the switch turned 
ON 
while the current is regulated at 8.3A 
by  adjusting the load to the generator. 
If 
the voltage  is within the  range from 
6V 
to 
14V, 
the voltage 
output is normal. 
Note 
: 
If 
a 
battery  is  connected 
as 
a 
load to the generator, the 
DC 
output voltage will increase by 
approximately 
I 
to 
2V. 
Therefore, carefully observe the electrolyte level and  do not overcharge 
the battery. 
- 
23 
- 