Product Manual

3-4 Receiving & Installation MN2417
Warning: Incorrect installation of this generator set could result in property damage, injury or death.
Connection of the generator to its fuel source must be done by a qualified professional
technician or contractor.
WARNING: Be sure the system is properly grounded before applying power. Do not apply AC power before
you ensure that grounds are connected. Electrical shock can cause serious or fatal injury. NEC
requires that the frame and exposed conductive surfaces (metal parts) be connected to an
approved earth ground. Local codes may also require proper grounding of generator systems.
Intended Use The intended purpose of this generator set is to provide electrical power when the main utility power
supply is interrupted. Therefore, it is important that all the wiring that connects the generator set with
your house, transfer switch, distribution box, battery charger, etc. be properly installed.
Protection Circuit protection is provided within the generator. The power output connections are rated and
sized according to the KW of the generator. Proper lead wire from these points to the automatic
transfer switch (or load switching device) is mandatory. See transfer switch information for
corresponding generator input terminals. Use only copper wires.
Table 3-3 Standby Power Ratings
Generator
Catalog
No.
Electrical Load Capacity Standby Power Ratings
1 Phase 3 Phase
kVA kW Volts Amps * kVA kW Volts Amps
TS25 18 18 240/120 75/2x75 25/25/25 20/20/20 208/240/480 69/60/30
TS35 25 25 240/120 104/2x104 37/37/37 30/30/30 208/240/480 104/90/45
TS45 27 27 240/120 112/x2112 46/48/48 37/38/38 208/240/480 128/114/57
TS60 43 43 240/120 179/2x179 60/61/61 48/49/49 208/240/480 166/146/73
TS80 45 45 240/120 187/2x187 74/80/80 59/64/64 208/240/480 205/192/96
TS130 78 78 240/120 325/2x325 125/127/127 100/101/101 208/240/480 347/301/152
TS175 100 100 240/120 416/2x416 169/188/188 135/150/150 208/240/480 468/450/225
TS225 150 150 240/120 625/2x625 225/225/225 180/180/180 208/240480 625/541/271
TS250 175 175 240/120 729/2x729 250/250/250 200/200/200 208/240/480 693/601/300
TS350 206 206 240/120 858/2x858 350/350/350 280/280/280 208/240/480 972/842/421
TS400 250 250 240/120 1041/2x1041 400/400/400 320/320/320 208/240/480 1110/962/481
TS500 250 250 240/120 1041/2x1041 500/500/500 400/400/400 208/240/480 1388/1203/601
* Example 2x75 means 2 lines (Line to Neutral) of 120V @ 75 amps each.
Table 3-4 Prime Power Ratings
Generator
Catalog
No.
Electrical Load Capacity Prime Power Ratings
1 Phase 3 Phase
kVA kW Volts Amps * kVA kW Volts Amps
TS25 18 18 240/120 75/2x75 23/23/23 18/18/18 208/240/480 62/54/27
TS35 22 22 240/120 92/2x92 33/33/33 27/27/27 208/240/480 93/81/41
TS45 25 25 240/120 104/2x104 44/44/44 35/35/35 208/240/480 121/105/53
TS60 40 40 240/120 167/2x167 56/56/56 45/45/45 208/240/480 156/135/68
TS80 41 41 240/120 171/2x171 67/73/73 54/58/58 208/240/480 187/174/87
TS130 76 76 240/120 317/2x317 113/115/115 90/92/92 208/240/480 312/277/138
TS175 90 90 240/120 375/2x375 138/156/156 110/125/125 208/240/480 382/376/188
TS225 135 135 240/120 562/2x562 200/200/200 160/160/160 208/240/480 555/481/241
TS250 160 160 240/120 667/2x667 227/227/227 180/180/180 208/240/480 625/541/271
TS350 187 187 240/120 779/2x779 319/319/319 255/255/255 208/240/480 885/767/383
TS400 240 240 240/120 1000/2x1000 365/365/365 292/292/292 208/240/480 1013/878/439
TS500 240 240 240/120 1000/2x1000 455/455/455 365/365/365 208/240/480 1266/1098/549
* Example 2x75 means 2 lines (Line to Neutral) of 75 amps each.