User's Manual
17
17
english
Power TP
Power TP
BIS L-400
Installation
Metal frame
Installation
BIS L-400
When installing two BIS L-400 on a metal base, there is normally no mutual interference. If
a metal frame is located in an unfavorable location, problems may result when reading out
the data carriers. In this case the read distance will be reduced to 80 % of the maximum
value.
Testing is recommended in critical applications!
Once a data carrier has been processed in front of a read head, the next data carrier must
wait 400 ms before being introduced into the active field. This can be implemented by
means of a stopper. If a stopper is not used, there is a rule of thumb which takes into
account the conveyor speed. Distance between the data carriers in m = (0.4 x conveyor
speed in m/s) + 0.25 m.
Example: Conveyor speed = 1 m/s
Distance = (0.4 x 1 m/s) + 0.25 m = 0.65 m
This is an approximation for the worst case.
When using small data carriers and/or small read heads, the distance is reduced considerably!
L-400_835996_0803_E.p65
18
english18
BIS L-400
Installation
Installation
BIS L-400,
permissible
distances
Distance from data carrier to data carrier
BIS L-200-03/L BIS L-201-03/L BIS L-202-03/L
BIS L-100-05/L BIS L-101-05/L BIS L-102-05/L
BIS  L-400  > 25 cm  > 30 cm  > 40 cm
Distance from read head to read head
The following distances must be maintained between the individual BIS L-400 systems:
X
Y
Distance X Distance Y
BIS L-405-...-001-... 1 m 1 m
BIS L-405-...-002-... 0.5 m 0.3 m
BIS L-405-...-003-... 0.5 m 0.3 m
BIS L-405-...-004-... 0.5 m 0.3 m