User's Manual

www.balluff.com 33
8.2 Parameterization
data mapping
CRC check
Data carrier
Setting the processor parameters
8
BIS L-409 IO-Link Device
Processor
Address 10hex, CRC_16 check
The CRC check is a procedure for determining a check value in order to be able to recognize
data transmission errors. If the CRC check is activated, an error message is sent when a CRC
error is detected.
(If the parameter CRC_16 data check is set, then in addition to the data carrier data, a 2-byte
CRC_16 checksum is checked (see “Data integrity” on page 15). The data compare counter is
automatically set to one-time reading. Detection of a data carrier arriving in the read zone then
takes a maximum of 70 ms.
Note
The CRC_16 data check can only be used with data carriers of type BIS L-10X-05/L.
The data carriers must be initialized using a BIS L-60_ _ processor and the
BISCOMRW.EXE PC software or a portable reader BIS L-81_ (refer to the User's
guide for the corresponding device for this procedure).
Checksum
The checksum is written to the data carrier as 2 bytes of information. This means 2 bytes of user
data per block are sacrificed.
1 byte, Address 10hex
MSB 6 5 4 3 2 1 LSB
(not relevant) 1/0
Bit 0 (LSB) = 0: no CRC check (default setting)
Bit 0 (LSB) = 1: CRC Check
Address 11hex, BIS L-10x-05
Note
If type BIS L-10X-05 data carriers are used, parameter “BIS L-10x-05” must be
activated.
1 byte, Address 11hex
MSB 6 5 4 3 2 1 LSB
(not relevant) 1/0
Bit 0 (LSB) = 0: No type BIS L-10x-05 data carrier is used (default setting)
Bit 0 (LSB) = 1: A type BIS L-10x-05 data carrier is used