User Manual
Table Of Contents
- LRP76 Long Range Passive Reader/Writer
- Table of Contents
- Getting Started
- Mechanical Specifications
- Power and Electrical Interface
- Configuration Menu
- Standard RFID Interface
- 5.1 Introduction
- 5.2 Command Timeout Values
- 5.3 Address Blocks
- 5.4 ABx Error Codes
- 5.5 Command Descriptions
- 5.6 ABx Standard Commands
- 5.6.1 Command 4 (04 Hex): Tag Fill
- 5.6.2 Command 5 (05 Hex): Block Read
- 5.6.3 Command 6 (06 Hex): Block Write
- 5.6.4 Command 7 (07H): Read Tag Serial Number
- 5.6.5 Command 8 (08 Hex): Tag Search
- 5.6.6 Command D (0D Hex): Start/Stop Continuous Block Read
- 5.6.7 Command E (0EH) Read SN and Data
- 5.6.8 Command F (0FH) Start/Stop Continuous Read SN and Data
- 5.7 ABx Fast Commands
- 5.7.1 ABx Command Packet Structure
- 5.7.2 Command 4 (04 Hex): Tag Fill
- 5.7.3 Command 5 (05 Hex): Block Read
- 5.7.4 Command 6 (06 Hex): Block Write
- 5.7.5 Command 7 (07H): Read Tag Serial Number
- 5.7.6 Command 8 (08 Hex): Tag Search
- 5.7.7 Command D (0D Hex): Start/Stop Continuous Block Read
- 5.7.8 Command E (0EH) Read SN and Data
- 5.7.9 Command F (0FH) Start/Stop Continuous Read SN and Data
- Technical Specifications
- Models and Accessories
- ASCII Chart
Standard RFID Interface
LRP76 Long Range Passive Reader/Writer 25
EXAMPLE
Writes 4 bytes of data to the tag starting at address 0001H. A timeout
of 2 seconds (07D0H = 2000 x 1 msec increments) is set for the
completion of the Block Write.
Command from the Host Response from the LRP76
MSB LSB Remarks MSB LSB Remarks
AAH 06H Perform Command 6 AAH 06H Command Echo
00H 01H Start Address = 0001H FFH FFH Message Terminator
00H 04H Write Length= 4 bytes
(0004H)
07H D0H Timeout value
00H 41H Write Data 1 = 41H
00H 46H Write Data 2 = 46H
00H 49H Write Data 3 = 49H
00H 44H Write Data 4 = 44H
FFH FFH Message Terminator