4. You must press CTRL-E within 7 seconds to enter the Interface
Board Monitor mode from a terminal emulator (EC) connected to
COM port 2 (9600, N, 8, 1). If the LRP830 does not receive
CTRL-E in the seven second period, it will automatically enter
"RUN MODE".
5. Upon entering CTRL-E, wait for the following menu to appear.
————————————————————————————
| HMS/LRP Rd/Wrt Controller with DeviceNet & Serial I/O. |
| (c) 2000 Escort Memory Systems, a Datalogic Co. |
————————————————————————————-
Commands:
I <cr> ———— Display Configuration Info
E <cr> ———— Edit Configuration Sub-menu
Z <cr> ———— Download Firmware Hex File (config defaults)
X <cr> ———— Download Firmware Hex File (retain config)
RESET ———— To enter Run Mode (exit monitor)
>x
Note: "X" is the recommended option for new firmware download by the user. No download option will
overwrite the DeviceNet serial number set at the factory (V2.0F and above). Commands are not case sen
-
sitive.
*:-D Initiate download now (do not restart prior to RESET msg.)*
CTRL-E places the main board in a special mode, that allows the Main
Board to pass communications to the interface board during Monitor Mode.
NOTE:
After Monitor Mode has been entered via CTRL-E within 7 seconds, you
must reset the device to enter Run Mode. Run Mode is entered automatically
if no control key actions are performed.