Cut Sheet

Table Of Contents
1
+
10–30 V dc
Gate
16–30 V dc
1.2 A Max.
234
5678
9
101314
F1
BROWN
BLUE
DRAIN (BARE)
BLACK
WHITE
EMITTER and
RECEIVER CABLES
V- V+
Power
12 11
NC NC NC NC
15 30
through
16 Solid-state Ouputs
150 mA Max each
4.5 System Power Wiring
Wire the system power.
1. Connect a 16 to 30V dc source to controller terminals #1 (V+) and #2 (V–).
2. Connect a good earth ground to terminal #3.
A good earth ground is important for providing electrical and RF noise immunity to the MINI-ARRAY System. The dc power source must
supply 1.25 amps (worst case) when using the longest (6 ) sensors. See Specicaons on page 7 for more informaon.
4.6 Gate Wiring
Connect a switched 10 to 30 V dc source as a gang input (if required) between controller terminal #11 (+) and #12 (-). Voltage is
typically switched by the open-collector output transistor of a dc sensing device.
4.7 Serial Communicaon Wiring
RS-485 (Models MAC-1, MACP-1, and MACN-1 only)— Connect RS-485 lines (if used) to terminals #13 (+) and #14 (-).
RS-232— Prepare an RS-232 cable using a DB-9 male connector with the connecons shown. DO NOT use a “null modem” RS-232 cable.
RS-232 via a DB9
Connecon Pin Descripon
5
1
9 6
2 Transmit (TX)
3 Receive (RX)
5 Ground (GND)