Installation guide

Sensor positions
threshold a programmable
% offset above the
presented condition
Threshold position
adjusted by
Manual Adjust
Darkest
(no signal)
Most Light
(saturated
signal)
Output OFF Output ON
Condition
Presented
Figure 7. Dark SET (Light Operate shown)
Dark SET and Manual Adjust
Moves switching threshold value up or down to make adjustments
Slide Mode switch to ADJ to enter Adjust mode
Press "+" to increase; press "-" to decrease
GREEN display shows the switching threshold value
2 seconds after adjustment, the GREEN display will flash 3 times to confirm
Slide Mode switch to RUN to complete operation
Remember: Manual adjustments are disabled when Auto Thresholds are ON
Follow these steps to perform a Dark SET:
Note: TEACH Selection must be programmed to dr SEt (see Program Mode on page
6 )
1. Enter Adjust Mode.
Method Action Result
SET Button
14
Set Mode switch to ADJ Display: Red - Signal Level; Green -
Threshold
Remote Input
15
No action required; sensor is ready for
Dark SET method
2. SET Sensing Condition.
14
SET Button: 0.04 seconds "Click" 0.8 seconds
15
Remote Input: 0.04 seconds T 0.8 seconds
DF-G1 Expert
Dual Display Fiber Amplifier