Instruction manual

Method Action Result
SET Button
Present sensing condition
Click the SET rocker button
Threshold Condition Accepted
Displays read "Lt SEt" then alternate
"PASS" with % Offset
13
; Sensor
returns to Adjust mode
Threshold Condition Not Accepted
Displays read "Lt SEt" then alternate
"FAIL" with minimum % Offset
13
for
sensing condition; Sensor returns to
Adjust mode
Remote Input
Present sensing condition
Single-pulse the remote input
T
3. Return to RUN Mode
Method Action Result
SET Button Move Mode switch to RUN Display: Red - Signal Level; Green -
Threshold
Remote Input No action required; sensor returns to
RUN mode automatically
6.5 Dark SET
Sets a threshold a programmable % offset above the presented condition
Any condition lighter than the threshold condition causes the output to change state
Threshold can be adjusted using "+" and "-" rocker button (Manual Adjust)
Recommended for applications where only one condition is known, for example a stable dark background with
varying lighter targets
See Program Mode on page 9 for programming the Offset Percent setting
NOTE: Offset Percent MUST be programmed to Minimum Offset to accept conditions of no signal (0
counts).
A single sensing condition is presented, and the sensor positions a threshold a programmable % offset above the
presented condition. When a condition lighter than the threshold is sensed, the output either turns ON or OFF, depending
on the LO/DO switch setting (see LO/DO Switch in Top Panel Interface on page
4).
13
See Troubleshooting on page
24 for more explanation of the % Offset displayed after the Light SET method
DF-G1 Expert
Dual Display Fiber Amplifier
20