Manual

M-GAGE
™
 S18M — Vehicle Detection Sensor
4 P/N 114430 rev. C   
Banner Engineering Corp. • Minneapolis, MN U.S.A.
www.bannerengineering.com  •  Tel: 763.544.3164
SMP1 Flex
Conduit Plug
¾" Flex
Conduit
2" PVC
Conduit
6" Below
Grade
Figure 2.  Below-grade installation 
3.
1.
2.
Below-Grade Installation
Materials
•  M-GAGE S18M Sensor
•  SMP1 Conduit Plug
•   2" Schedule 80 rigid PVC conduit (1.5" may be used if there 
is only one 90° bend); total length and number of elbows 
depend on installation layout
•  2" (or 1.5") rigid PVC end cap (1 per installation)
•   ¾" I.D. flexible, liquid-tight, non-metallic conduit (same 
length as PVC conduit used for application)
•  DPB1 Portable Programming Box
Procedure
1)   Lay out 2" (or 1.5") PVC in the desired configuration. For 
the best sensor performance, the sensing location (located 
at the end of the conduit run) should be 6" below the final 
surface. Provide an access point where the PVC comes 
above grade (where the sensor and flex conduit can be fed 
in or pulled out, as required).
2)   Secure the end cap to the PVC, at the sensing location.
3)   Measure the overall length of the PVC run, from the 
sensing location to the control panel.
4)   Cut a section of ¾" flex conduit to span the total distance 
from the control panel to the sensing location.
5)   Thread the sensor into the SMP1 conduit plug. Feed the 
sensor cable into the flex conduit, until the sensor and plug 
are snugly seated in the end of the flex conduit.
6)   Feed the flex conduit by hand, sensor-end first, into the 
PVC access point until the sensor reaches the PVC end cap.
7)   Secure the remaining flex conduit from the access point to 
the control cabinet.
8)   After the sensor is configured (see following section), wire 
the sensor into the control device and power supply per the 
wiring diagram on page 8.
Above-Grade Installation
Materials
•  M-GAGE S18M Sensor
•  SMP2 Conduit Plug
•   ¾" Schedule 40 PVC electrical conduit; total length and 
number of elbows depend on installation layout 
•  Electrician’s fishtape
•  Silicone adhesive
•  DPB1 Portable Programming Box
Procedure
1)   Mount the PVC electrical conduit from the sensing point 
to the control panel. Plastic conduit should be used for at 
least the first 6.1 m (20') from the sensing point; metal or 
flexible conduit may be used the remainder of the distance.
2)   Thread the S18M sensor into the threads of the SMP2 
conduit plug.
3)   Feed the fishtape into the conduit, from the control panel 
towards the sensing point.
4)   Pull the sensor cable back through the conduit, until the 
sensor almost reaches the end of the plastic conduit. Do 
NOT pull sensor into conduit.
5)   Apply a small amount of silicone adhesive to the outside of 
the conduit at the sensing point end.
6)  Press the conduit plug into the end of the conduit.
7)   After the sensor is configured (see following section), wire 
the sensor into the control device and power supply per the 
wiring diagram on page 8.
Figure 3. Above-grade installation 
SMP2 Conduit Plug
¾" PVC Conduit
2.
1.