Instruction Manual

Instruction Manual
Compact IO-Link device to analog converter that outputs an analog value, voltage or
current, as presented by the IO-Link master
The converter also connects to an analog source, voltage or current, and outputs the
value to the IO-Link master and as a representative PFM output
4-pin M12 male quick-disconnect connector supports IO-Link
Two 4-pin M12 female quick-disconnect connectors that each support analog inputs
and outputs
Rugged over-molded design meets IP65, IP67, and IP68
Connects directly to a sensor or anywhere in-line for ease of use
Models
Housing
R45
C = Converter
Q = Integral M12 quick disconnect
Q
Connector
Female 1
II = Analog 1 Current In/Current Out
UU = Analog 1 Voltage In/Voltage Out
Male
C II
Female 2
II = Analog 2 Current In/Current Out
UU = Analog 2 Voltage In/Voltage Out
IIK
Function
- -
K = IO-Link
Note: Available models are analog current in/out, and analog voltage in/out.
Overview
Analog In
When an analog input value is received by this converter, the numerical representational value is sent to an IO-Link Master via Process Data In (PDI).
PDI Analog Ranges:
Voltage = 0 mV to 10,000 mV
Current = 4,000 µA to 20,000 µA
Analog Out
This converter also allows for the user to output an analog value by sending the numerical analog value from the IO-Link Master via Process Data
Out (PDO).
PDO Analog Ranges:
Voltage = 0 mV to 11,000 mV
Current = 0 µA to 24,000 µA
PDO Outside Valid Range (POVR)
If the PDO value sent to this converter is outside of the PDO Analog Range value, then the actual analog output value will be set to the one of the
three selectable POVR levels after a 2 second delay:
Low (default): 0 V or 3.5 mA
High: 10.5 V or 20.5 mA
Hold: Level retains previous value indefinitely
Note: If a connected IO-Link sensor is changed back to SIO mode, then the previous value will be held.
PFM Out
Enables a PFM representation of an analog input as an output.
PFM Input Source Channel
Selects the analog input value from Port 1 or Port 2 as the PFM output source.
Pulse Frequency Configuration
Sets the near and far frequency values.
R45C IO-Link to Dual Analog Input-Output
Converter
Original Document
228480 Rev. A
14 December 2022
228480

Summary of content (5 pages)