Specifications
General
Power*
+10 to 30V dc
For European applications: +10 to 24V dc, ± 10%
Power Consumption
Lessthan1.4W(60mA)at24Vdc
Mounting
#10orM5(M5hardwareincluded)
M5FastenersMax.TighteningTorque
0.56N•m(5in•lbf)
Case Material
Polycarbonate
Weight
0.26kg(0.57lb.)
Indicators
Two LED, bi-color
Switches
Two Push Buttons
Display
Six Character LCD
External Cable Glands
FourPG-7type,One1/2NPTtype
Cable Glands Max. Tightening Torque
0.56N•m(5in•lbf)
* ForEuropeanapplications,powertheDX80fromaLimitedPowerSourceasdenedinEN60950-1.
It is Banner Engineering’s intent to fully comply with all national and regional regulations regarding radio frequency emissions. Customers who want to re-export this
product to a country other than that to which it was sold must ensure that the device is approved in the destination country. A list of approved countries appears in the
SureCross DX80 Wireless Product Manual, in the Agency Certifications section. Consult with Banner Engineering if the destination country is not on this list.
Radio
Range*
900 MHz: Up to 4.8 kilometers (3 miles)
2.4 GHz: Up to 3.2 kilometers (2 miles)
Transmit Power
900 MHz: 21 dBm Conducted
2.4 GHz: 18 dBm Conducted, ≤ 20 dBm EIRP
Spread Spectrum Technology
FHSS (Frequency Hopping Spread Spectrum)
Antenna Connector
Ext.ReversePolaritySMA,50Ohms
Antenna Max. Tightening Torque
0.45N•m(4in•lbf)
Link Timeout
8 seconds
* With the standard 2 dB antenna. High-gain antennas are available, but the range depends on the environment and line of sight. To determine the range of your wireless
network, perform a Site Survey.
Many parameters are configurable. The values in the tables represent factory defaults unless otherwise noted.
Inputs
Analog Inputs
Four, 0 to 20 mA (Gateway); Two, 0 to 20 mA (Node)
Analog Input Sample Rate
125milliseconds
Analog Report Rate
1 second or on Change of State (1% change in value)
Accuracy
0.1% of full scale +0.01% per ºC
Outputs
Analog Outputs
Four, 0 to 20 mA (Gateway); Two, 0 to 20 mA (Node)
Analog Update Rate
62.5milliseconds
Output State Following Timeout
De-energized (OFF)
Accuracy
0.1% of full scale +0.01% per ºC