Manual

Banner Engineering Corp.•Minneapolis,MNU.S.A
www.bannerengineering.com•Tel:763.544.3164
2 P/N 136441 rev. B
SureCross™ DX80K Wireless Configured Kit
Hookup Diagrams
For additional information, including installation and setup, weatherproofing, device menu
maps, troubleshooting, and a list of accessories, please refer to the SureCross™ Wireless I/O
Network product manual, Banner p/n 132607.
I/O
Point
Terminal
Block Label
DX80 Gateway DX80 Node Terminal
Block Label
I/O
Point
1 AI1 Analog IN 1 Analog OUT 1 AO1 9
2 AI2 Analog IN 2 Analog OUT 2 AO2 10
3 AI3 Analog IN 3 Analog OUT 3 AO3 11
4 AI4 Analog IN 4 Analog OUT 4 AO4 12
9 AO1 Analog OUT 1 Analog IN 1 AI1 1
10 AO2 Analog OUT 2 Analog IN 2 AI2 2
11 AO3 Analog OUT 3 Analog IN 3 AI3 3
12 AO4 Analog OUT 4 Analog IN 4 AI4 4
Configured input/output mapping
Analog Sourcing Input Wiring
Analog Sourcing Output Wiring
PWR
GND
CM4
CM3
AO4
AO3
AO2
AO1
PWR
GND
CM2
CM1
AI4
AI3
AI2
AI1
PWR
AIx
*
* Do not exceed analog input ratings for analog
inputs. Only connect sensor outputs to analog inputs.
AOx
GND
+10 to 30V dc
5-pin Euro-style Hookup (RS-485)
Wire Color Gateway 10–30V dc Node
1 Brown +10 to 30V dc Input +10 to 30V dc Input
2 White RS485/D1/B/+
3 Blue dc common (GND) dc common (GND)
4 Black RS485/D0/A/
5 Gray Comms grnd
* Connecting dc power to the communication pins will cause permanent damage.