Manual

Configurable Gateway with discrete and analog inputs and outputs
IP67 Base
2.4 GHz
IP20 Base
900 MHz
Internal antenna models are also
available, but are not UL Listed. For
more information, contact your local
Banner Engineering Corp. represen-
tative.
The SureCross® wireless system is a radio frequency network with integrated I/O that can oper-
ate in most environments and eliminate the need for wiring runs. Wireless networks are formed
around a Gateway, which acts as the wireless network master device, and one or more Nodes.
Wireless industrial I/O device with four selectable discrete inputs, four sourcing discrete out-
puts, two 0 to 20 mA analog inputs, and two 0 to 20 mA analog outputs
10 to 30V dc power input
DIP switches for user configuration
Modbus serial interface
Site Survey analyzes the network’s signal strength and reliability and displays the results on
the Gateway's LCD
Frequency Hopping Spread Spectrum (FHSS) technology and Time Division Multiple Access
(TDMA) control architecture ensure reliable data delivery within the unlicensed Industrial, Sci-
entific, and Medical (ISM) band
Transceivers provide bidirectional communication between the Gateway and Node, including
fully acknowledged data transmission
Lost RF links are detected and relevant outputs set to user-defined conditions
The DX80...C models are certified for use in Class I, Division 2, Group A, B, C, D; Zone 2
(Category 3G) Hazardous Locations when properly installed in accordance with the National
Electrical Code, the Canadian Electrical Code, or applicable local codes/regulations (see
Specifications)
Model Frequency Environmental Rating I/O
DX80G9M6S4P4M2M2
900 MHz ISM
Band
IP67, NEMA 6
Inputs: Four selectable discrete, two 0 to 20 mA
analog
Outputs: Four sourcing discrete, two 0 to 20 mA
analog
DX80G2M6S4P4M2M2 2.4 GHz ISM Band
DX80G9M6S4P4M2M2C
900 MHz ISM
Band
IP20, NEMA 1
Class I, Division 2, Group A, B,
C, D Hazardous Locations (see
Specifications)
DX80G2M6S4P4M2M2C 2.4 GHz ISM Band
WARNING: Not To Be Used for Personnel Protection
Never use this device as a sensing device for personnel protection. Doing so could lead to serious
injury or death. This device does not include the self-checking redundant circuitry necessary to allow its
use in personnel safety applications. A sensor failure or malfunction can cause either an energized or de-
energized sensor output condition.
The SureCross® DX80 Wireless Network
Gateway
Node
Node
FlexPower Node
and Battery Supply Module
The SureCross® DX80 wireless I/O network provides reliable moni-
toring without wiring or conduit installation. The SureCross wireless
network operates independently or in conjunction with a host system,
PLC, and/or PC software.
Each wireless network system consists of one Gateway and one or
more Nodes. Devices ship with factory-defined discrete, analog, or a
mix of discrete and analog inputs and outputs.
The SureCross® DX80 network is a deterministic system—the net-
work identifies when the radio signal is lost and drives relevant out-
SureCross DX80 Gateway with Discrete and Analog I/O
P/N 131935 Rev. H 5/23/2013
0 131935 4

Summary of content (8 pages)