DIP Switch Configurable Gateway for the M-GAGE Node
Features
IP67 Base
2.4 GHz
IP20 Base
900 MHz
The SureCross wireless system is a radio frequency network with integrated I/O that
can operate in most environments while eliminating the need for wiring runs. Systems are
built around a Gateway, which acts as the wireless network master device, and one or
more Nodes.
Gateway’s discrete inputs are mapped to baseline two M-GAGE Nodes; M-GAGE
inputs are mapped to the Gateway’s outputs
Switch configurable to allow for user programmability of two M-GAGE Nodes
10 to 30V dc power input
Modbus serial interface
Site Survey analyzes the network’s signal strength and reliability
Frequency Hopping Spread Spectrum (FHSS) technology and Time Division Multiple
Access (TDMA) control architecture combine to ensure reliable data delivery within
the unlicensed Industrial, Scientific, and Medical (ISM) band
Transceivers provide bidirectional communication between the Gateway and Node, in-
cluding fully acknowledged data transmission
Lost link outputs on the Gateway
The DX80...C models are certified for use in Class I, Division 2, Group A, B, C, D;
Zone 2 (Group IIC) Hazardous Locations when properly installed in accordance with
the National Electrical Code, the Canadian Electrical Code, LCIE/ATEX, or applicable
local codes/regulations (see Specifications)
For additional information, the most recent version of all documentation, and a complete
list of accessories, refer to Banner Engineering's website, www.bannerengineering.com/
surecross.
Models
Model Frequency Environmental Rating I/O
DX80G9M6S6P6ZP 900 MHz ISM Band
IP67, NEMA 6
Inputs: Selectable discrete
Outputs: Sourcing discrete
DX80G2M6S6P6ZP 2.4 GHz ISM Band
DX80G9M6S6P6ZPC 900 MHz ISM Band IP20, NEMA 1
Class I, Division 2, Group A, B, C, D
Hazardous Locations (see Specifica-
tions)
DX80G2M6S6P6ZPC 2.4 GHz ISM Band
Internal antenna models are also available, but are not UL Listed. For more information, contact your local Banner Engineering Corp.
representative.
WARNING: Not To Be Used for Personnel Protection
Never use this product as a sensing device for personnel protection. Doing so could lead to seri-
ous injury or death. This product does NOT include the self-checking redundant circuitry necessary to
allow its use in personnel safety applications. A sensor failure or malfunction can cause either an ener-