LED Behavior for the Nodes
After powering up and binding the Gateway and its Nodes, verify all devices are communicating properly. A Node will not sample its
inputs until it is communicating with its Gateway. When testing communication between the Gateway and Node, all radios and antennas
should be at least two meters apart or the communications may fail.
LED 1 LED 2 Node Status
(flashing green)
Radio Link Ok
(flashing red) (flashing red)
Device Error
(flashing red, 1 per 3 sec)
No Radio Link
Supported RTD Types
The RTD Node supports up to four 3-wire RTD inputs by default. Additional types are available with configuration.
Thermocouple
Range °F Range °C
Pt100 (DIN 0.00385) -328 to 900 °F -200 to 482 °C
Cu 10 Ohm (alpha = 0.00427) -328 to 500 °F -200 to 260 °C
* For the copper RTD, the best accuracy is when measuring between −50 to +150 °C (−58 to +302 °F). Below this range, expect errors
approaching 3% of reading. Above this range, expect errors approaching 0.5% of reading.
Modbus Register Table (High Resolution Mode)
I/O
Modbus Holding Register I/O Type Units I/O Range Holding Register Rep-
resentation
Terminal Block
Labels
Gateway Any Node Min. Max. Min. (Dec.) Max. (Dec.)
1 1 1 + (Node# × 16)
2 2 2 + (Node# × 16)
3 3 3 + (Node# × 16) RTD 1
°F/°C -1638.3 +1638.4 -32768 32767
A1+/A1-/DI1
4 4 4 + (Node# × 16) RTD 2 A2+/A2-/DI2
5 5 5 + (Node# × 16) RTD 3 A3+/A3-/DO1
6 6 6 + (Node# × 16) RTD 4 A4+/A4-/DO2
7 7 7 + (Node# × 16) Reserved
8 8 8 + (Node# × 16) Device Message
...
15 15 15 + (Node# × 16) Control Message
16 16 16 + (Node# × 16) Reserved
In high resolution mode, the temperature = (Modbus register value) ÷ 20. In low resolution mode, the temperature is (Modbus register
value) ÷ 2.
Temperature values are stored as signed values in the Modbus register. A 0 in the register is interpreted as 0°; and -32767 (65535
unsigned) in the register (0xFFFF) is interpreted as −1 ÷ 20 = −0.05° in high resolution mode and −1 ÷ 2 = −0.5° in low resolution mode.
Specifications
SureCross DX80 FlexPower Node with RTD Inputs
P/N 131597 Rev. I www.bannerengineering.com - tel: 763-544-3164 5