Owner's manual

Radio and General
Radio Range
900 MHz: Up to 4.8 kilometers (3 miles)
2.4 GHz: Up to 3.2 kilometers (2 miles)
Radio Transmit Power
900 MHz: 21 dBm conducted
2.4 GHz: 18 dBm conducted, less than or equal to 20
dBm EIRP
900 MHz Compliance (150 mW Radios)
FCC ID TGUDX80 - This device complies with FCC
Part 15, Subpart C, 15.247
IC: 7044A-DX8009
2.4 GHz Compliance
FCC ID UE300DX80-2400 - This device complies with
FCC Part 15, Subpart C, 15.247
ETSI/EN: In accordance with EN 300 328: V1.7.1
(2006-05)
IC: 7044A-DX8024
Spread Spectrum Technology
FHSS (Frequency Hopping Spread Spectrum)
Link Timeout
Gateway: Configurable
Node: Defined by Gateway
Radio range is with the 2 dB antenna that ships with the product.
High-gain antennas are available, but the range depends on the
environment and line of sight. To determine the range of your wire-
less network, perform a Site Survey.
Power
Requirements: +10 to 30V dc or +3.6 to 5.5V dc low
power option (Outside the USA: +12 to 24V dc, ±10%
or +3.6 to 5.5V dc low power option)
Consumption: Less than 1.4 W (60 mA) at 24V dc
Housing
Polycarbonate housing and rotary dial cover; polyester
labels; EDPM rubber cover gasket; nitrile rubber, non-
sulphur cured button covers
Weight: 0.26 kg (0.57 lbs)
Mounting: #10 or M5 (SS M5 hardware included)
Max. Tightening Torque: 0.56 N·m (5 lbf·in)
Antenna Connection
Ext. Reverse Polarity SMA, 50 Ohms
Max Tightening Torque: 0.45 N·m (4 lbf·in)
Interface
Indicators: Two bi-color LEDs
Buttons: Two
Display: Six character LCD
Wiring Access
Four PG-7, One 1/2-inch NPT, One 5-pin Euro-style
male connector
For European applications, power the DX80 from a Limited Power
Source as defined in EN 60950-1.
Inputs
RTD Inputs
Sample Rate: 1 second
Report Rate: 16 seconds
Accuracy: 0.1% of full scale
Resolution: 0.1 °C, 15-bit
Environmental
Rating
DX80 Models:IEC IP67; NEMA 6; (See UL section be-
low for any applicable UL specifications)
DX80...C Models: IEC IP20; NEMA 1 (In a suitable en-
closure: Class I, Division 2, Group A, B, C, D; T4 −40
to 80 °C)
Operating Environment
Temperature: −40 to +85 °C (Electronics); −20 to +80
°C (LCD)
Humidity: 95% max. relative (non-condensing)
Radiated Immunity: 10 V/m, 80-2700 MHz
(EN61000-6-2)
Shock and Vibration
IEC 68-2-6 and IEC 68-2-7
Shock: 30g, 11 millisecond half sine wave, 18 shocks
Vibration: 0.5 mm p-p, 10 to 60 Hz
Refer to the SureCross DX80 Wireless I/O Network Product Man-
ual (p/n 132607) for installation and waterproofing instructions. Op-
erating the devices at the maximum operating conditions for exten-
ded periods can shorten the life of the device.
SureCross DX80 FlexPower Node with RTD Inputs
6 www.bannerengineering.com - tel: 763-544-3164 P/N 131597 Rev. I