Owner manual

Banner Engineering Corp., 9714 Tenth Ave. No., Minneapolis, MN USA 55441 • Phone: 763.544.3164 • www.bannerengineering.com • Email: sensors@bannerengineering.com
SureCross® DX80 and Performance Models
Quick Start Guide
A set-up guide for the SureCross DX80 and Performance wireless systems
Stop!
Read these instructions before using your SureCross
radios. Do not discard these instructions.
For more detailed information about installing and using your SureCross products, download and
read the SureCross Wireless I/O Network Manual, p/n 132607.
Step 2: Activate Extended Addressing Mode (SureCross DX80
Models)
If the label on the face of your radio does not say Performance, you will need to activate
extended addressing mode.
1. Disconnect all radios from their power sources.
2. Remove the top covers of the Gateway and all its Nodes.
3. Move DIP switch 1 to the ON position.
Check the datasheet of your specific radio for any additional DIP switches applicable to your
installation.
p/n 128185 rev. J
Step 1: Select 1 Watt or 250 mW Mode (SureCross
Performance 900 MHz Models only)
For SureCross Performance 2.4 GHz radios, skip to Step 3.
If the label on the face of your radio does not say Performance, skip to step 2 to activate
extended addressing mode.
By default, SureCross Performance 900 MHz radios are configured to transmit at 1 Watt. If
you are mixing Performance models within the same network as non-Performance radios, you
must operate in 250 mW mode.
1. Disconnect all radios from their power sources.
2. If you are using Performance radios within a DX80 network, move DIP switch 1 to
the ON position to select 250 mW (DX80 compatibility mode).
Check the datasheet of your specific radio for any additional DIP switches applicable to your
installation.
Switch 1
WARNING . . . Not To Be Used for Personnel Protection
Never use these products as sensing devices for personnel protection. Doing so could lead to serious injury
or death.
These devices do NOT include the self-checking redundant circuitry necessary to allow their use in personnel
safety applications. A device failure or malfunction can cause either an energized or de-energized output
condition. Consult your current Banner Safety Products catalog for safety products that meet OSHA, ANSI, and
IEC standards for personnel protection.
Important: Never Operate 1 Watt
Radios Without Antennas.
To avoid damaging the radio circuitry, never power up
SureCross Performance or SureCross MultiHop (1 Watt)
radios without an antenna.

Summary of content (4 pages)