Instruction Manual

Configurable Node with analog inputs and analog outputs
IP67 Base
2.4 GHz
IP20 Base
900 MHz
The SureCross® wireless system is a radio frequency network with integrated I/O that can
operate in most environments and eliminate the need for wiring runs. Wireless networks are
formed around a Gateway, which acts as the wireless network master device, and one or
more Nodes.
Wireless industrial I/O device with four 0 to 10V analog inputs and four 0 to 10V analog
outputs
10 to 30V dc power input
DIP switches for user configuration
Frequency Hopping Spread Spectrum (FHSS) technology and Time Division Multiple Ac-
cess (TDMA) control architecture ensure reliable data delivery within the unlicensed Indus-
trial, Scientific, and Medical (ISM) band
Transceivers provide bidirectional communication between the Gateway and Node, includ-
ing fully acknowledged data transmission
Lost RF links are detected and relevant outputs set to user-defined conditions
The DX80...C models are certified for use in Class I, Division 2, Group A, B, C, D; Zone 2
(Category 3G) Hazardous Locations when properly installed in accordance with the Na-
tional Electrical Code, the Canadian Electrical Code, or applicable local codes/regulations
(see Specifications)
For additional information, updated documentation, and accessories, refer to Banner Engineering's website, www.bannerengineer-
ing.com/surecross.
Models Frequency Environmental Rating I/O
DX80N9X6S0P0V4V4 900 MHz ISM Band
IP67, NEMA 6
Inputs: Four 0 to 10V analog
Outputs: Four 0 to 10V analog
DX80N2X6S0P0V4V4 2.4 GHz ISM Band
DX80N9X6S0P0V4V4C 900 MHz ISM Band IP20, NEMA 1
Class I, Division 2, Group A, B, C, D
Hazardous Locations (see Specifica-
tions)
DX80N2X6S0P0V4V4C 2.4 GHz ISM Band
Internal antenna models are also available, but are not UL Listed. For more information, contact your local Banner Engineering Corp.
representative.
WARNING: Not To Be Used for Personnel Protection
Never use this device as a sensing device for personnel protection. Doing so could lead to serious
injury or death. This device does not include the self-checking redundant circuitry necessary to allow its
use in personnel safety applications. A sensor failure or malfunction can cause either an energized or de-
energized sensor output condition.
SureCross User Configuration Tool
The User Configuration Tool (UCT) offers an easy way to link I/O points in your wire-
less network, view I/O register values graphically, and set system communication pa-
rameters when a host system is not part of the wireless network.
The UCT requires a special USB to RS-485 (model number BWA-UCT-900 for 1 Watt
radios, BWA-HW-006 can be used for all other radios) converter cable to pass infor-
mation between your computer and the Gateway. Download the most recent revi-
sions of the UCT software from Banner Engineering's website: http://www.banneren-
gineering.com/wireless.
SureCross DX80 Node
P/N 136326 Rev. E 5/22/2013
0 136326 5

Summary of content (8 pages)