Owner's manual
T18XDN Series
4 P/N 47797 rev. C
Banner Engineering Corp. • Minneapolis, MN U.S.A.
www.bannerengineering.com • Tel: 763.544.3164
Specifications
Supply Voltage and Current
Supply Protection Circuitry
Protected against reverse polarity and transient voltages
Output Protection Circuitry
Protected against false pulse on power-up and continuous overload or short-circuit of outputs
Output Response Time
Opposed: 3.5 milliseconds ON and 2.0 milliseconds OFF
Polarized Retro and Fixed-Field: 3.5 milliseconds ON and OFF
NOTE: 100 millisecond delay on power-up; outputs do not conduct during this time.
Indicators
Two LEDs: a bi-colored (Red/Green) LED and a Yellow LED
A bi-color LED indicates the status of the network:
Green ON Steady = Sensor on line, connected to master
Green Flashing = Sensor on line, address + baud rate are ok
Red ON Steady = Critical network fault or duplicate node address detected; wrong baud rate
Red Flashing = Minor or connection time-out fault
Yellow ON Steady = Normally open output is conducting
Yellow Flashing = Excess gain marginal (1-1.5x) in light condition
Repeatability
Opposed: 575 microseconds
Polarized Retro and Fixed-Field: 950 microseconds
Repeatability and response are independent of signal strength
Sensor Configuration
The following features of the T18XDN Series Sensors are programmable via the network with a configuration
tool:
Feature Range (default)
Network Address 0-63 (63)
Baud Rate 125K, 250K, 500K (125K)
Operation Mode Light Operate or Dark Operate (Light Operate)
All T18XDN models support:
Explicit Message Connection: Required to Set and Get sensor Attributes
Change of State Connection (COS): which responds to a slave’s change of state.
I/O Response is with the following 8-bit word of data:
Bit: 0: 0 Output is OFF
1 Output is ON
Bit 1: 0 Alarm output is OFF
1 Alarm output is ON
Bits 2-7 Not Used: Always 0
Note: Configuration may be simplified through use of an Electronic Data Sheet (Banner model EDS 40223)
Environmental Rating
Leakproof design rated NEMA 6P; IEC IP67
Connections
5-pin Euro-style DeviceNet compatible quick-disconnect fitting; cables are ordered separately - interlinkBT
Operating Temperature
-25° to +70°C (-13° to 158°F); Maximum relative humidity 90% at 50°C (non-condensing)
Vibration and
Mechanical Shock
All models meet Mil. Std. 202F requirements. Method 201A (Vibration; frequency 10 to 60 Hz, max.,
double amplitude 0.06-inch acceleration 10G). Method 213B conditions H&I (Shock: 75G with unit
operating; 100G for non-operation)
11 to 25V dc (10% maximum ripple); Supply current (exclusive of load current):
Opposed Mode Emitter: 25 mA
Opposed Mode Receiver: 45 mA
Polarized & Non Polarized Retro: 55 mA
Diffuse: 55 mA
Fixed-Field: 60 mA
Construction
Housings are PBT thermoplastic polyester; lenses are polycarbonate (opposed models) or acrylic (retro and
fixed-field models); T18XDN comes with one jam nut