Brochure

R527 Series, R528 Series (2368-5xx Series)
96
© Copyright 2006 TAC. All Rights Reserved. F-27383-1
TAC PNEUMODULAR
£
Electric-Pneumatic Relays
Model Chart
Specifications
The electric-pneumatic relays are three-way,
two-position, electrically activated air valves for
use in pneumatic control systems where the
application requires a variety of switching,
diverting, or interlocking functions, actuated by an
electrical circuit. The R527 Series switches one
SPDT pneumatic circuit, while the R528 Series are
designed with DPDT pneumatic switching
(switches two independent SPDT pneumatic
circuits simultaneously).
Features:
R527 Series provides SPDT pneumatic switching (N.C.,
N.O., C).
R528 Series provides DPDT pneumatic switching (N.C.,
N.O., C), plus (N.C.2, N.O.2, C2). Switches two separate
circuits simultaneously.
Manual/auto switch (permits control system testing without
starting and stopping electrical equipment).
All ports clearly labeled. Ports align with MCS-S terminals.
TAC PNEUMODULAR: Must be mounted on MCS-Socket
and used with MCS-EC electrical connector.
Model No.
Wholesale
Model No.
Coil
Voltage
Switch
Action
R527-24DC 2368-500 24 Vdc
SPDT
R527-24 2368-501 24 Vac
R527-110 2368-502 110 Vac
R527-230 2368-503 208 to 240 Vac
R528-24DC 2368-520 24 Vdc
DPDT
R528-24 2368-521 24 Vac
R528-110 2368-522 110 Vac
R528-230 2368-523 208 to 240 Vac
Output 3 to 15 psig.
Action
SPDT models (R527 Series) Coil de-energized, C and NO are connected. Coil energized, C and NC are connected.
DPDT models (R528 Series)
Coil de-energized, C and NO are connected, C2 and NO2 are connected. Coil energized, C and NC
are connected, C2 and NC2 are connected.
Maximum ambient temperature 140qF (60qC).
Supply air pressure Clean, dry, oil free air required (Ref. EN-123).
Nominal 20 to 25 psig (138 to 172 kPa).
Maximum 30 psig (207 kPa).
Connections
Air Barbed fittings for 1/4 in. O.D. polyethylene or 5/32 in. I.D. polyurethane tubing.
Electrical
Purchase separately the MCS-EC contact assembly with screw terminals and the MCS-EB electrical
barrier.
R527
Series,
R528
Series
(2368-5x
x
Series)
MNONC C S
AUTO
M
AN
UAL