Brochure

R527 Series, R528 Series (2368-5xx Series)
F-27383-1 © Copyright 2006 TAC. All Rights Reserved. 97
Specifications (Continued)
Accessories
Typical Applications
Figure 1 Typical Application.
Air consumption 1728 scim (471.7 mL/s).
Air flow capacity 1728 scim (471.7 mL/s).
Power consumption 2.2 VA.
Adjustments Auto, manual switch.
Mounting Designed for use on MCS-S manifold socket only.
Dimensions 4-1/8 H x 1-1/32 W x 2-55/64 D in. (105 x 50 x 63 mm).
Active Connections
Port Connected to
M Main air.
CCommon.
C2
a
a
DPDT models only.
NOTE: A loss of main air pressure will have the same effect as de-energizing the coil.
Common no. 2.
NO Normally open.
NO2
a
Normally open no. 2
NC Normally closed.
NC2
a
Normally closed no. 2.
Model No. Wholesale Model No. Description
MCS-EC 22-122 Electrical contact assembly.
MCS-EB 22-136 Electrical barrier.
CNONC
R527-110
Electric-Pneumatic Relay
M M
M
M
B
CRMS
Branch Air to
Control Device
Temperature
Transmitter
3-15 psig
120 Vac
Wire to Fan Starter
P541
Receiver Controller
N100-0010