Brochure

T150 Series (2252 Series)
Model Chart (Continued)
Specifications
Accessories
Typical Applications
Figure 1 Typical Application.
Model No.
Wholesale
Model No.
Range
(non-adjustable)
qF (qC)
Span
qF
(qC)
Mounting Sensing Element Description
T150-1046 2252-703
-40 to 160
(-40 to 71)
200
(111)
Duct or
outdoor air
Replaces TKS-2031. 1/4 x 2.5 in. (6 x 64 mm) bulb with 42 in.
(1.1 m) capillary
T150-1054 2252-151
-25 to 125
(-32 to 52)
150
(84)
Duct or
outdoor air
4 x 1/4 in. (102 x 6 mm) bulb with 3 ft. (0.9 m) capillary
T150-1055 2252-655 10-1/2 x 1/4 in. (267 x 6 mm) bulb with 9 ft. (2.7 m) capillary
T150-1062 2252-662
30 to 80
(-1 to 27)
50
(28)
Duct
Averaging element, 20 ft. long (6 m)
T150-1073 2252-273
50 to 100
(10 to 38)
Rigid (coiled) element, 10 in. long (25.4 cm)
T150-1082 2252-701
50 to 150
(10 to 66)
100
(56)
Duct
Replaces TKS-4017. Averaging element, 20 ft. long (6.1 m).
T150-1083 2252-702
Replaces TKS-9017. Rigid (coiled) element, 10 in. long
(25.4 cm)
Action Direct, proportional.
Adjustments None required, factory calibrated.
Supply air pressure Clean, dry, oil free air required (Ref. EN-123).
Nominal 20 psig r0.5 psi (138 kPa r3.4 kPa) through 1.0 scfh restrictor.
Maximum 30 psig (207 kPa).
Output pressure 3 to 15 psig (21 to 103 kPa).
Air connection 1/8 in. -27 FNPT.
Maximum case ambient temperature 140qF (60qC).
Construction Copper element, cast aluminum base, zinc plated steel cover.
Mounting Duct or immersion (refer to Model Chart).
Weight 0.9 lb (0.4 kg).
Case dimensions 2-5/8 H x 3-1/16 W x 1-3/4 D in. (67 x 78 x 44 mm).
Model No. Wholesale Model No. Description
100-13 20-777 Sun shield for sensing bulbs.
100-17
a
a
Use together for copper well with extended neck.
20-778 3/8 x 7-1/32 in. copper well with 1/2 in. NPT bushing.
100-25 20-782 3/8 x 10-17/32 in. copper well with 1/2 in. NPT bushing.
100-47
a
20-803 Neck extension adaptor - converts 7-1/32 in. well to 10-17/32 in. well.
100-49 20-805 3/8 x 7-1/32 in. Stainless steel well with 1/2 in. NPT bushing (includes 20-803).
100-71 22-401 Adapter, brass, for mounting T150 immersion transmitter in Barber-Colman AT-201 or AT-203 well.
N4-32 20-944 Restrictor tee, copper tubing.
N100-0010 21-038 Restrictor tee, polyethylene tubing.
N100-2501 21-153 In-line restrictor.
B
CRMS
Receiver Controller
M
M
N100-0010
T150
Pneumatic
Temperature
Transmitter
3-15
p
si
g
Branch Air to
Control Device
© Copyright 2006 TAC. All Rights Reserved. F-27383-1
132