Brochure

TKS-5001, TKS-5001-600, TKS-6001
154
© Copyright 2006 TAC. All Rights Reserved. F-27383-1
Room and Light Troffer Temperature Transmitters
Model Chart
Specifications
For proportional temperature control used with
RKS Series receiver-controllers. May be used with
one or more calibrated gauges for continuous
temperature indication at any local or remote
position.
Features:
Force balance pneumatic feedback provides stable
operation.
Highly sensitive bimetal sensing element.
Three different models to suit various applications.
Model No. Mounting
Range
(Non-Adj.)
qF (qC)
Span
qF (qC)
Sensing Element
Description
Cover
Ambient
Temperature
Limits
qF (qC)
Air
Connections
Dimensions
H x W x D
in. (mm)
TKS-5001 Wall
a
a
Order fittings separately for type of wall construction.
50 to 100
(10 to 38)
50 (28) Bimetal
Beige
Plastic
Shipping:
-40 to 150
(-40 to 65)
Operating:
50 to 100
(10 to 38)
5/32 in. dia.
spring
reinforced
plastic tube
4-3/8 x 2-3/4 x 1-5/8
(111 x 70 x 41)
TKS-5001-600 Aspirating
Brushed
chrome
Barbed
fittings for 1/4
in. plastic
tubes
5 x 3-1/2 x 2-1/2
(127 x 89 x 64)
Cover: 5-1/2 x 4 (140 x 102)
TKS-6001 Light Troffer
a
N.A.
5/32 in. dia.
spring
reinforced
plastic tube
3/8 x 3/8 x 3
(10 x 10 x 76)
Ambient temperature Refer to Model Chart.
Output air signal 3 to 15 psig (21 to 103 kPa).
Action Direct.
Supply air pressure Clean, oil free, dry air required (reference EN-123).
Nominal 20 psig (138 kPa) through 0.0075 in. (190 Pm) restrictor.
Minimum 18 psig (124 kPa).
Maximum 30 psig (207 kPa).
Air consumption for sizing air
compressor
41.5 scim (11.3 mL/s). TKS-5001-600, 69.1 scim (18.9 mL/s).
Air capacity for sizing air mains 36 scim (13.2 mL/s). TKS-5001-600, 88 scim (24 mL/s).
TKS
-
5001
TKS-5001
600,
TKS-6001
TK
S
-
6001
TK
S
-
500
1-
600
TKS-5001