Brochure

AKS-1100
F-27383-1 © Copyright 2006 TAC. All Rights Reserved. 13
Receiver Controller Setpoint Adjuster and Scale Plates
Model Chart
Specifications
Setpoint adjuster and scale plates used to provide
remote setpoint adjustment of RKS-2001, RKS-
4002, and RKSR-4000 receiver-controllers. May
also be used to manually pilot pneumatic relays.
Features:
Allows the setpoint of a pneumatic receiver-controller to be
raised or lowered from a location up to 1000 ft. (305 m)
from the receiver-controller.
Series available to work with various transmitter ranges.
A receiver gauge, mounted near the setpoint adjuster
shows the actual result of remotely adjusting the receiver-
controller’s setpoint.
Model No. Description
AKS-1100 Remote setpoint adjuster.
Construction Aluminum housing, precision flapper-nozzle assembly.
Output Linear 3 to 15 psig (21 to 102 kPa).
Air pressure Clean, oil free, dry air required (reference EN-123).
Maximum 30 psig (207 kPa).
Ambient limits
Shipping temperatures -40 to 150qF (-40 to 65qC).
Operating temperatures 40 to 120qF (4 to 49qC).
Humidity 5 to 95% RH, non-condensing.
Air connection Barbed connection for 1/4 in. O.D. plastic tubing.
Air consumption for sizing air
compressor
41.5 scim (11.3 mL/s).
Air capacity for sizing air mains 48 scim (13.1 mL/s).
Mounting Panel or wall box. Panel requires 5/8 in. (16 mm) hole for mounting the remote setpoint adjuster.
Panel space required 2-3/8 H x 2-1/4 W x 2-1/2 D in. (60 x 57 x 63 mm).
AKS-11xx scale plates (must be
ordered separately)
White letters on black background, keyed for proper locating on setpoint adjuster.
AKS
-
1100
AK
S
-11
00
with
S
cale Plat
e