Brochure

HKS-2033, HKS-5033
38
© Copyright 2006 TAC. All Rights Reserved. F-27383-1
Room/Duct Humidity Transmitters
Model Chart
Specifications
For proportional humidity control used with RKS
Series receiver-controllers. May be used with
calibrated gauges for continuous humidity
indication at any local or remote position.
Features:
HKS-2033
10 to 90% relative humidly range for 3 to 15 psig (20.7 to
103.4 kPa) output.
Highly sensitive nylon sensing element, designed for duct
insertion.
Pneumatic feedback for stable, repeatable operation.
HKS-5033
10 to 90% relative humidity range for 3 to 15 psig (20.7 to
103.4 kPa) output.
Highly sensitive nylon sensing element, designed for
wall-mounting.
Pneumatic feedback for stable, repeatable operation.
Matches appearance of TK-Series thermostats.
Model No. Description
HKS-2033 Duct humidity transmitter.
HKS-5033 Room humidity transmitter.
Sensing element Nylon.
Sensing
Span 80% RH.
Range 10 to 90% RH (non-adjustable).
Output air signal 3 to 15 psig (21 to 103 kPa).
Action Direct.
Ambient limits
Shipping -40 to 150qF (-40 to 65qC). 0 to 98% RH, non-condensing.
Operating
-20 to 125qF (-29to52qC). 10 to 98% RH, non-condensing. 10 to 2500 fpm (0.05 to 12.7 m/s)
sensed air velocity.
Supply air pressure Clean, oil free, dry air required (reference EN-123).
Nominal 20 psig (138 kPa) through 0.0075 in. (190 Pm) restrictor.
Minimum 18 psig (124 kPa).
Maximum 30 psig (207 kPa).
Air connections
HKS-2033 Barbed for 1/4 in. O.D. plastic tubing.
HKS-5033 5/32 in. diameter spring reinforced plastic tubing.
Air consumption for sizing air
compressor
41.5 scim (11.3 mL/s).
Air capacity for sizing air mains 48 scim (13.2 mL/s).
HKS
-
2033
HKS-503
3
HKS-2033
HKS-5033