User Guide

Table Of Contents
F-26895-4 © Copyright 2010 Schneider Electric All Rights Reserved. 3
Installation
AM-704 Power Supply Supply Voltage: 24 Vac ± 15%
24 Vdc ± 15%
Power Consumption <1 Watt
Transformer Sizing 2 VA
Input
-Isolation
-Type
-Trigger level
-time between trigger
pulses
-Impedance
-Pulse duration/resolu-
tion
-Range 1
-Range 2
-Range 3
-Range 4
Optically isolated (when wired as such)
Normal or triac, jumper selectable
12 to 24 Vac/Vdc or dry contact to com
12.5 milliseconds minimum
Vac - 500 Ω, Vdc - 10 Ω
Four selectable ranges, in seconds or dry contact or SSR
closure ± 40% of signal increment
0.0235 to 6 seconds/in 0.0235 sec increments
0.0196 to 5 seconds in 0.0196 sec increments
0.1 to 25.5 seconds/ in 0.100 sec increments
0.59 to 2.93 seconds/ in 0.0092 sec increments
Output Voltage:
Current:
Accuracy:
2 to 10 Vdc
15 mA max
± 2%
Electrical Connection Wire terminals, 14 gauge max.
Ambient temperature -20 to 150°F (-30 to 65° C)
Operating Humidity 5 to 95% RH non-condensing
Mounting Snap-Track (provided)
Dimensions Board:
W/ snap-track
2-3/16” x 2-3/16” x 9/16”
2-3/8” x 2-1/4” x 15/16”
Weight 1.5 oz.
AM-705, AM-706 Power Supply 24 Vac ± 20%, 50/60 Hz, 24 Vdc ± 10%
Transformer Sizing 1 VA
Control Signal Y 0 to 10 Vdc, 2 to 10 Vdc (switchable)
Power Output Up to 10 actuators (1 mA max)
Degree of Protection AM-705 only NEMA 4 (IP54)
Connection Terminals (14 gauge wire max)
Humidity 5 to 95% RH non-condensing
AM-708 Resistance 500 Ω
Length 9"