User Guide

Table Of Contents
4 © Copyright 2010 Schneider Electric All Rights Reserved. F-26895-4
AM-703
Set the circuit board jumper to fit the application.
The AM-703 may also be used to sequence several actuators from one signal source. This
is done by adjusting multiple modules to work at different input ranges. (Example: 2 to 5 Vdc,
5 to 8 Vdc, 8 to 11 Vdc, etc.)
Calibration
1. Attach a variable signal source to the AM-703 input and power wires.
2. Apply power.
3. Input the minimum signal level.
4. Adjust the offset potentiometer to produce a 2 Vdc signal at the output. A clockwise
rotation of the potentiometer screw will increase the output signal. See Figure-2.
5. Input the maximum signal level.
6. Adjust the span adjustment to produce a 10 Vdc signal at the output. A clockwise
rotation of the potentiometer screw will increase the output signal. See Figure-2.
7. Double check the input-output calibration and install.
AM-704
1. Set the input pulse timing jumpers.
Jumper not
connected to
both pins for
voltage applications
(as shipped)
Jumper on both
pins for
4 to 20 mA
applications
Figure-1 Jumper Settings.
Span Adjustment
Zero Offset
Adjustment
Figure-2 Calibration Adjustments.
Range 1
10
A
B
Range 2
10
A
B
Range 3
10
A
B
Range 3
10
A
B
Position Clock Rate
Range 1
Range 2
Range 3
Range 4
Figure-3 Timing Jumper Settings.
0.0235 to 6 seconds in
0.0235 sec. increments
0.0196 to 5 seconds in
0.0196 sec. increments
0.1 to 25.5 seconds in
0.100 sec. increments
0.59 to 2.93 seconds in
0.0092 sec. increments