Brochure

RKS-1001, RKS-2001, RKS-3002, RKS-4002, RKS-5001, RKSR-4000
110
© Copyright 2006 TAC. All Rights Reserved. F-27383-1
Single/Dual Transmitter Input Receiver Controllers
Model Chart
Specifications
For use in conjunction with remote proportional
transmitters for proportional control of pneumatic
actuated dampers, valves, etc., in air conditioning
systems. The transmitter-receiver-controller
system may be used to control temperature,
humidity, or pressure.
Features:
Nozzle and flapper relay-type receiver controllers.
Linear, stable and responsive.
Models available for one, two or three inputs.
Mounting provided for two (1/8 NPT) 1-1/2 in.
stem-mounted receiver-gauges and two 1-1/2 in.
stem-mounted pressure gauges.
Barbed fittings for 1/4 in O.D. plastic tubing.
Setpoint scales available to match transmitter ranges.
Model No. Description Remote SPA
Action
a
a
D.A. (Direct Acting) factory shipped: increases output pressure on rise in input 1 pressure. Field changeable to R.A.
R.A. (Reverse Acting): decreases output pressure on rise in input 1 pressure.
Type
Authority
b
b
Primary transmitter connects to input 1.
Proportional Band
RKS-5001
Single input
None
D.A./R.A.
One Pipe
None
4% to 40% of input transmitter
span adjustable
RKS-1001
Two Pipe
2-1/2% to 40% of primary
(input 1) transmitter span
adjustable
RKS-2001
r10% of primary
transmitter span
RKS-3002
Dual input
c
c
Input 2 has a reverse acting reset only. For direct acting the output pressure increases as input 2 increases. For reverse acting the output pressure
increases as input 2 decreases.
None
10% to 200% of primary
(input 1) transmitter span
adjustable
RKS-4002
r10% of primary
transmitter span
RKSR-4000
Replacement single
or dual input
Receiver-controller Forced balanced pneumatic amplifier.
Setpoint Adjustable, qF, qC, in. water, mm water, % relative humidity labels (included with controller).
Proportional band Field adjustable (refer to Model Chart).
Input signals 3 to 15 psig (21 to 103 kPa). Maximum input pressure 30 psig (207 kPa).
Output air signal 0.5 psig (3.4 kPa) to supply air pressure -0.5 psig (-3.4 kPa).
Action Direct. Field changeable to reverse (refer to Model Chart).
RKS
-
1001
RKS-200
1
RKS-300
2
RKS-400
2
RKS-500
1
RKSR-
4000
RKS-1001
(Shown without AKS-4 Cover)
RKS-5001
RKSR-4000