Typical Applications
Figure 1 Typical Piping for RKS-5001 Receiver-Controller.
Figure 2 Typical Piping for RKS-3002, RKS-4002, RKSR-4000 Dual Input Receiver-Controller
(External Restrictors for the Transmitters).
Figure 3 Typical Piping for RKS-3002, RKS-4002, RKSR-4000 Dual Input Receiver-Controller
(Internal Restrictors for the Transmitters).
NOTES: These apply to all RKS Series Receiver-Controllers:
1.When internal restrictors are used, the transmitter must be located within 200 ft. (61 m) of the receiver-controller.
2.When external restrictors are used, the transmitter must be located within 1000 ft. (305 m) of the receiver-controller,
and the restrictor must be located within 200 ft. (61 m) of the transmitter (preferably at the transmitter’s location).
Remove internal restrictors from receiver-controller and install blocking gaskets.
M
Trans
D.A.
B1
B2
RKS-5001
Receiver Controller
M
M
1 Only one output is available at a time.
R.A.
Damper Actuator
Damper Actuator
Transmitter
Restrictor Tee
M
Trans
D.A.
B1
B2
RKS-5001
Receiver Controller
M
R.A.
Damper Actuator
Damper Actuator
Transmitter
A1MB 2
RKS-3002, RKS-4002, RKSR-4000
Receiver Controller
M
M
M
1 Shown with external restrictors for transmitters.
To Actuator
Primary
Transmitter
Restrictor Tee
Restrictor Tee
Secondary
Transmitter
A1MB 2
RKS-3002, RKS-4002, RKSR-4000
Receiver Controller
M
1 Shown using internal restrictors for
transmitters of Receiver Controller.
To
Actuator
Primary
Transmitter
Secondary
Transmitter