Brochure

S510, S511 Series (2390 Series)
Specifications (Continued)
Accessories
Typical Applications
Figure 1 S510 Typical Application.
Figure 2 S511 Series Typical Application.
Connections Barbed fittings for 1/4 in. O.D. polyethylene or 5/32 in. I.D. polyurethane tubing.
Air consumption 28.8 scim (7.9 mL/s).
Air capacity 230.4 scim (62.9 mL/s).
Mounting
Designed for use on MCS-S manifold socket. These devices can also be mounted on a panel face or
surface mounted by using the appropriate mounting bracket (refer to Accessories).
Dimensions
S510 2-1/16 H x 1-7/8 W x 3-1/4 D in. (52 x 48 x 83 mm).
S511-5, S511-10 2-1/16 H x 1-7/8 W x 3-1/2 D in. (52 x 48 x 89 mm).
Dial Plates for S510, S511-5, and S511-10
Model No.
Wholesale
Model No.
Dial Markings
50-01 22-301 Warmer, arrow clockwise.
50-02 22-302 Warmer, arrow counterclockwise.
50-03 22-303 Increase, arrow clockwise.
50-04 22-304 Increase, arrow counterclockwise.
50-05 22-305 0 to 100.
50-06 22-306 Blank.
50-51 22-351 10 divisions.
50-53 22-353 0 to 20 psig.
Model No. Wholesale Model No. Description
50-xx Dial Plates (refer to Dial Plates for S510, S511-5, and S511-10 Table).
TOOL-082 5/64 in. hexhead wrench.
Mounting Brackets
K511 22-155 Single switch bracket.
K512 22-156 One switch and one 2 in. gauge bracket.
K514 22-157 Two switches and two 2 in. gauge brackets.
S510
Gradual Switch
MB
M
MM
B
CRMS
P541
Receiver Controller (DA)
N100-0010
Temperature
Transmitter
(3-15 psig)
Branch Air to
Control Device
S511 Gradual Switch
Damper Minimum Position
MS1B
B
CRMS
P541
Receiver Controller (DA)
M
M M
To E/P Relay and
Damper Actuators
N100-0010
Temperature
Transmitter
(3-15 psig)