These switches are manually operated devices
adaptable to a wide variety of applications in
pneumatic control systems. They are normally
used to perform diverting or supply and exhaust
functions to operate final control components or
index relays in multiple switching systems.
The S520 is a two-position, four-branch switch. The
S521 is a two-position five-branch switch that
provides one blocked port in each knob position.
The S530 is a three-position, four-branch switch
which can be used to supply a signal to any one of
three devices or supply any one of three signals to
a device. Its unused ports are blocked. The S531 is
identical except for its unused ports being
exhausted to atmosphere.
The S540 and S541 are four-position, five-branch
switches which follow the same operating pattern
as the S530 Series. However, they can supply a
signal to any one of four devices or vice-versa.
Unused ports are blocked in the S540 and
exhausted in the S541.
Features:
S520, S530, S540 Series Selector Switches can easily be
mounted any of three ways:
Flush-mounted on panel face. Dial plate locks onto switch
body and is held in place by tightening the mounting nut
from the rear. Provides exposed adjustment.
Mounted with two screws and MCS-G Gasket to MCS-S
Socket. Provides concealed adjustment.
Mounted remotely on the various mounting brackets listed.
K511, K512 and K514 “flush-mount” the gradual switches
with or without flush-mounted 2 in. pressure gauges.
TAC PNEUMODULAR: All parts clearly labeled. Ports align
with MCS-S terminals.
Model No.
Wholesale
Model No.
Description
S520 2392-504 Two-position, four-branch.
S521 2392-505 Two-position, five-branch (one blocked port in each knob position).
S530 2393-504 Three-position, four-branch (unused ports blocked).
S531 2393-505 Three-position, four-branch (unused ports exhausted).
S540 2394-504 Four-position, five-branch (unused ports blocked).
S541 2394-505 Four-position, five-branch (unused ports exhausted).
S52
x
Series,
S53x
Series,
S54x