T12 through T33 Series (2211 through 2218 Series)
Specifications
T-Series Thermostat Kits
Kit Model Chart
Part Number Parts Description
T1x-3081
T1x-3011 Thermostat with factory installed dial stop
10-11 Tubing assembly
10-58 Mounting ring
10-77 Adaptor plate
B-262 (was N4-109) 1/4 x 3/16 in. reducer
C3-46 Cover kit
T1x-3091
T1x-3011 Thermostat with factory installed dial stop
RC-3-181 Cover insert
C3-42 Cover
N5-95 Thermostat conversion kit
2211-41x
2212-41x
221x-41x Thermostat
20-714 Wall plate
20-042 Mounting plate and screws
20-693 Tubing
2890-011 Convertible cover
2211-51x
2212-51x
2214-52x
2216-526
2218-53x
221x-5xx Thermostat with factory installed dial stop
21-933 Full dial cover with blank cover conversion
22-022 Conversion kit
Action Proportional; refer to Model Chart.
Setpoint range 55 to 85qF (13 to 29qC).
Throttling range
2 to 12qF/12 psi (-17 to-11qC/83 kPa) adjustable, factory set 3qF (-16 qC)(night, 3 to 5qF/12 psi
(-16 to -15qC/83 kPa), non-adjustable).
Construction
Components Die cast aluminum, stainless steel, and glass-filled nylon.
Diaphragms Fabric-reinforced neoprene.
Air filter Internal.
Supply air pressure Clean, dry, oil free air required (Refer to EN-123).
Nominal Refer to Model Chart and Typical Applications.
Maximum 30 psig (207 kPa).
Connections For spring-reinforced 3/16 in. plastic tubing and required fittings. Order separately.
Air consumption Refer to Model Chart and Typical Applications.
Calibration point
9 psig branch line pressure when ambient temperature equals setpoint (except T32 Series and
T33-301, 12 psig branch line pressure).
Setpoint adjustment Serrated thumbwheel, external or concealed.
Mounting Upright position on wall.
Dimensions 2-1/32 H x 2-1/32 W x 1-3/8 D in. (52 x 52 x 35 mm).