Brochure

T35-301, T36-301 (2212-318, 2212-319)
Specifications (Continued)
Accessories
For additional information, refer to Accessories page 636.
Typical Applications
Figure 1 Typical Application.
Construction
Components Die cast aluminum, stainless steel, and glass-filled nylon.
Diaphragms Fabric-reinforced neoprene.
Air filter Internal.
Supply air pressure Clean, dry, oil free air required (Refer to EN-123).
Operating 20 psig (138 kPa).
Maximum 30 psig (207 kPa).
Connections For spring-reinforced 3/16 in. plastic tubing and required fittings (order separately).
Air consumption 29.4 scim at 20 psig (8.0 mL/s at 172 kPa) main air pressure.
Calibration point
Deadband output Factory set at 8 psig (adjustable).
Direct acting T35-301 Heating: 4 psig (28 kPa) at setpoint. Cooling: 10.5 psig (72 kPa) at setpoint.
Reverse acting T36-301 Cooling: 4 psig (28 kPa) at setpoint. Heating: 10.5 psig (72 kPa) at setpoint.
Cover options See CT-x1, CTR-x1 for cover options (order separately).
Setpoint adjustment Individual concealed adjustments or heating and cooling by means o N2-4 calibration tool.
Mounting Upright position on wall.
Dimensions 2-1/32 H x 2-1/32 W x 1-3/8 D in. (52 x 52 x 35 mm).
Model No. Wholesale Model No. Description
6-371 20-642 Mounting ring (use with mounting heads).
10-15 20-695 Aspirating box, two pipe.
10-53 20-707 Metal thermostat guard.
10-57 20-710 Mortar joint fitting, two tube, copper.
10-58 20-711 Mounting ring (use with N5-52).
10-59 20-712 Internal stop kit.
10-62 20-715 Thermostat guard, clear Lexan
£
.
10-63 20-716 Insulating backplate, for plastic guards.
10-64 Tubing assembly with eyelets and fittings.
10-66 21-468 Mortar joint fitting, two “FR” tubes.
10-72 21-800 Concealed adjustment cover (black), for metal covers.
10-73 21-473 Drywall mounting fitting (snap-in).
10-76 21-876 Thermostat guard, opaque ABS.
10-77 20-714 Adaptor plate.
10-78  Insulating backplate.
10-80  Concealed adjustment cover, for use with gray ABS cover.
10-81 Concealed adjustment cover, for use with beige ABS cover.
10-82 20-850 Mounting plate for 2 x 4 switch box, Black.
10-82-SS Stainless steel.
10-82-47 Beige.
10-82-48 Euro-white.
MCS-GA 22-138 Gauge tap adaptor.
N2-4 20-881 Calibration tool for thermostats, (and P341, P541 and P541-RA).
N5-49 21-065 Adaptor (for use with N5-53).
N5-52 21-068 Bracket, drywall mount (use with 10-58 mounting ring).
N5-53 21-069 Bracket, stud mount rough-in.
N5-95  Wall thermostat conversion kit.
 22-022 Thermostat conversion kit.
 900-002 Thermostat calibration kit.
See Thermostat Covers section starting on page page 25.
For additional information, refer to Accessories page 157
T35-301
Thermostat
VV
MB
Heating
Valve N.O.
Cooling
Valve N.C.
M
3
4
3 Heating setpoint settings range from 2 to 6 psig,
3 to 6 psig, or 3 to 7 psig.
4 Cooling setpoint setting range is 8 to 13 psig.
© Copyright 2006 TAC. All Rights Reserved. F-27383-1