Brochure

AK-52101
F-27383-1 © Copyright 2006 TAC. All Rights Reserved. 9
Differential Logic Module Relay
Model Chart
Specifications
Pneumatic differential logic module relay typically
used for comparison of outdoor and return air
enthalpy transmitters to position the outdoor and
return air dampers, providing energy conservation,
when the outdoor air enthalpy is higher than the
return air enthalpy.
Features:
Compares two pneumatic signals; provides a high-gain
pneumatic output pressure change based on the input signal
comparison.
Model No. Input Pressures Output Pressure
AK-52101
“1” equal or less than input “2” Less than 3 psig (21 kPa).
“1” greater than input “2
Greater than 13 psig (90 kPa) when supply to portM” is 15 psig (103 kPa) or higher.
Max. output, supply at port “M”.
Output pressure vs. input pressures Refer to Model Chart.
Construction
Housing Base, zinc plated steel; cover, aluminum.
Relay diaphragm Neoprene coated, continuous fabric.
Bias adjustment Compensation for transmitter input and system variations.
Air pressure Clean, oil free, dry air required (reference EN-123).
Maximum 30 psig (207 kPa).
Ambient limits
Shipping temperatures -40 to 150qF (-40 to 65qC).
Operating temperatures 40 to 150qF (4 to 65qC).
Humidity 0 to 98% RH, non-condensing.
Air connection code Refer to Figure 1.
Air connections Barbed for 1/4 in. O.D. plastic tubing.
Air consumption for sizing air
compressor
41.5 scim(11.3 mL/s) at 20 psig (138 kPa). When supplied by a controller 0 scim (0 mL/s).
Air capacity for sizing air mains 48 scim (13.2 mL/s) at 20 psig (138 kPa) supply.
Mounting Panel or wall, three mounting holes are provided for No. 8 or No. 10 screws.
Dimensions 6 H x 3-3/8 W x 3-1/16 D in. (152 x 86 x 78 mm).
AK
-