N100-25xx Series
64
© Copyright 2006 TAC. All Rights Reserved. F-27383-1
Pneumatic Limit Controls
Model Chart
Specifications
Typical Applications
Figure 1 Typical Application.
Accessories
These controls open an integral pneumatic switch
when sensed temperature reaches the control
setpoint.
Features:
Reduces installation cost when temperature sensing point
is located a considerable distance from the motor starter of
an air-handling unit supply fan.
N100-2509 and N100-2513 respond when any one foot of
the 20 foot sensing element drops below setpoint.
If used with DPDT P/E Switch, one circuit of P/E can (for
example) open to de-energize a fan motor starter, while the
other circuit closes to initiate an alarm.
Model No. Description
N100-2509
a
a
All devices require N100-0010, N4-32, or N100-2501 restrictor.
15 to 55qF (-9 to 13qC). Pneumatic low limit, manual reset. Differential 5F degrees (2.7C degrees).
N100-2513
a
Same as N100-2509, but automatic reset. Differential 5F degrees (2.78C degrees).
Dimensions 3-63/64 H x 4-3/8 W x 2-9/32 D in. (101 x 112 x 58 mm). Note: dimensions do not include coil.
Restrictor Requires one N100-0010, N-32, or N100-2501.
Model No. Description
N4-32 Restrictor, 1/4 in. O.D. compression.
N100-0010 Restrictor tee for plastic tubing.
N100-2501 Restrictor, inline.
N100
-
25
x
x
Series
D
E
G
.
F
A
H
R
DEG
.F
AH
R
C
U
T
I
N
C
U
T
O
U
T
5
5
4
5
3
5
2
5
5
0
4
0
3
0
2
0
1
5
P
U
SH
T
O
RE
S
E
T
C
NO
N100-2513
Wire in series with the unit starter.
M
Restrictor
N100-2509
15/55 F
set: 35 F