Brochure

P301 Series (2301 Series)
Pressure Transmitters
Model Chart
Specifications
Accessories
Typical Applications
The pneumatic pressure transmitters are designed to measure either air
or fluid pressures. All models transmit a fixed-span, 3 to 15 psig output
signal proportional to input pressure to controlling and indicating devices
such as receiver-controllers, receiver gauges, and certain pneumatic
relays and alarm devices. These transmitters are available in various
pressure ranges to meet most control system application requirements.
Features:
Single-input pressure transmitter permits remote readout on receiver gauge, and
control of air, water, steam or refrigerant pressure from a convenient location.
Three different ranges permit proper match of transmitter range to application.
Quality design and construction assure linearity and responsiveness.
Factory-adjusted span and “zero”.
Field-assemble “zero” adjustment.
Model No.
Wholesale
Model No.
Input Pressure Range (psig) Maximum Safe Pressure (psig)
P301-040 2301-040
a
a
Includes one each 2”, 2-1/2” and 3-1/2” gauge overlay in the appropriate range.
-10 to +40 65
P301-150 2301-150
a
0 to 150 185
P301-300 2301-300
a
0 to 300 350
Output 3 to 15 psig.
Control Action Direct, proportional.
Maximum ambient temperature 140qF (60qC).
Supply air pressure Clean, dry, oil free air required (refer. EN-123).
Nominal 20 psig r0.5 psig.
Maximum 30 psig.
Connections Two 1/8 in. -27 FNPT.
Air consumption 27.7 scim (7.5 mL/s).
Air capacity 48 scim.
Adjustments Minor “zero” adjustment only.
Calibration None; factory calibrated.
Mounting External mounting ears are provided for easy mounting to panels or ducts.
Dimensions 2-5/8 H x 3-1/16 W x 1-3/4 D in. (66 x 78 x 45 mm).
Weight 15 oz.
Model No. Wholesale Model No. Description
N4-32 20-944 Tee restrictor for copper or plastic tubing.
N100-0010 21-038 Tee restrictor for plastic tubing.
N100-2501 21-153 In-line restrictor.
2890-001 2” overlay kit.
2890-002 2-1/2” overlay kit.
2890-003 3-1/2” overlay kit.
P301
Series
(2301
Series
)
B
CRMS
1
M M
1 Receiver Gauge scale to match Transmitter
P541
Receiver Controller
N100-0010
P301
Pressure
Transmitter
To Final
Control Device
Figure 1 Typical Piping Diagram.
F-27383-1 © Copyright 2006 TAC. All Rights Reserved. 69