Brochure

R436
Typical Applications
Figure 2 Typical Applications.
Positive Only
Lower Negative
Higher Positive
Negative Only
Higher Negative
Lower Positive
Diaphragm
Status
Alarm
To prove excessive air flow or pressure
NC
NO
C
Status
Alarm
To prove insufficient air flow or pressure
NC
NO
C
Diaphragm Connections
Refer to figure below. For positive pressure only, connect sampling
line to port E; port F remains open to atmosphere.
For negative pressure only, connect sample line to port F; port E
remains open to the atmosphere.
Two positive samples; connect higher pressure to port E and lower
pressure to port F.
Two negative samples; connect more negative sample to port E;
less negative to port E.
One positive and one negative; positive to port E; negative to port F.
Electrical
Before any pressure is applied to the
diaphragm, the switch contact rests in the
N.C. position (see figure below). Upon
application of sufficient pressure to actuate
the switch, the contact transfers to the N.O.
position. Connect control, status, and/or
alarm circuits, as shown.
EF