Selection Guide

22 Copyright 2008 TAC All Rights Reserved. F-26752-12
Actuator Specifications and Valve Assembly Mounting Dimensions
Valve Assemblies with MF41-6043, MS41-6043, MF41-6083, and MS41-6083 Actuators
Note: Standard Linked Valve Assemblies use the basic MF41-6043, MS41-6043, MF41-6083, and MS41-6083 actuators.
Specifications for the non-standard Mx41-6043/6083-502, -510, -520, -522 actuators are provided here for reference. Linked
Valve Assemblies using these non-standard actuators may be special-ordered by contacting the factory or field-mounted using
the AV-60x linkage kit for globe valve assemblies.
Actuator Specifications
Inputs
Control Signal MF41-6043 and MF41-6083 — Floating three-position control, 24 Vac.
MS41-6043 and MS41-6083 — Proportional, 0 to 10 Vdc; input resistance 100 k.
Control signal adjustment available with MS41-6043/6083-520 and MS41-6043/6083-522:
Start point (offset) — Between 0 and 5 Vdc (factory setting = 0 Vdc)
Span — 2 to 30 Vdc
Power Requirements All 24 Vac circuits are Class 2.
Connections 3 ft. (0.9 m) long, 18 AWG leads, plenum-rated.
Motor Type Synchronous
Outputs
Electrical Feedback potentiometer available for MF41-6043/6083-510: 0 to 1000 < 10 mA
Position feedback voltage for MS41-6043/6083: 0 to 10 Vdc, 1 mA
Auxiliary Switches: Dual auxiliary switches available with MF41-6043/6083-502,
MS41-6043/6083-502, MF41-6043/6083-522 and MS41-6043/6083-522:
Mechanical Output torque rating: 35 lb-in. (4 N-m) for Mx41-6043; 70 lb-in. (8 N-m) for Mx41-6083
Stroke: Normal angle of rotation is 90°, limited to a maximum of 95°. Field adjustable to limit
travel on either end of stroke.
Position indicator: Adjustable pointer is provided for position indication.
Output shaft setscrew: Tightening torque 55 to 60 lb-in. (6.3 to 6.8 N-m).
Environment
Temperature Limits Shipping and storage: -40 to 158 °F (-40 to 70 °C) ambient.
Operating: Minimum allowable valve fluid temperature: 20 °F (-7 °C).
Maximum allowable ambient: -25 to 130 °F (-32 to 55 °C) maximum ambient at
maximum valve fluid temperature of 250 °F (121 °C).
Humidity 5 to 95% RH, non-condensing.
Locations NEMA Type 2 (IEC IP54).
Agency Listings (Actuator)
UL UL-873, Underwriters Laboratories.
cUL Canadian Standards C22.2 No. 24-93.
European Community EMC Directive (89/336/EEC). Emissions (EN50081-1). Immunity (EN50081-2).
Part Number
Power Input @ 50/60 Hz
Voltage
a
a
24 Vac +20/-10% for ambient temperatures 90 to 130 °F (Mx41-6083 only).
Running VA Holding VA Watts
MF41-6043 and MF41-6083 24 Vac +20/-15% 2.3 2.0
MS41-6043 and MS41-6083 24 Vac +20/-15% 3.3 1.2 3.0
AC Rating: 24 Vac, 4 A resistive, 2 A inductive Switching hysteresis:
DC Rating: 12 to 30 Vdc, DC 2 A Switch Range:
Switch A — 0 to 90° range in 5° intervals
Recommended range usage — 0 to 45°
Factory setting — 5°
Switch B — 0 to 90° range in 5° intervals
Recommended range usage — 45 to 90°
Factory setting — 85°
Timing:
Part
Number
Timing in Sec.
At 60 Hz At 50 Hz
MF41-6043
MS41-6043
90 108
MF41-6083
MS41-6083
125 150