Selection Guide
Table Of Contents
- Selection Guide Contents
- Features and Benefits
- Features
- Benefits
- Linked Globe Valve Assembly
- Actuator/Linkage Assemblies for Globe Valves
- System Design Considerations
- Installation Considerations
- Valve/Actuator Combinations
- Linked Globe Valve Assemblies Specifications
- Actuator Specifications and Valve Assembly Mounting Dimensions
- Actuator Specifications
- Dimensions - 1/2” to 2” Globe Valve Assemblies
- Actuator Specifications
- Dimensions - 1/2” to 2” Globe Valve Assemblies
- Dimensions - 2-1/2” and 3” Screwed Globe Valve Assemblies
- Dimensions - 2-1/2” to 4” Flanged Globe Valve Assemblies
- Actuator Specifications
- Dimensions - 5” and 6” Flanged Globe Valve Assemblies
- Actuator Specifications
- Dimensions - 1/2” to 2” Globe Valve Assemblies
- Actuator Specifications
- Dimensions - 1/2” to 2” Globe Valve Assemblies
- Dimensions - 2-1/2” and 3” Screwed Globe Valve Assemblies
- Dimensions - 2-1/2” to 6” Flanged Globe Valve Assemblies
- Actuator Specifications
- Dimensions - 1/2” to 2” Globe Valve Assemblies
- Dimensions - 2-1/2” and 3” Screwed Globe Valve Assemblies
- Dimensions - 2-1/2” to 6” Flanged Globe Valve Assemblies
F-26752-12 Copyright 2008 TAC All Rights Reserved. 25
Valve Assemblies with Mx41-6153 Non-Spring Return Actuators
Actuator Specifications
Inputs
Control Signal MF41-6153— Three-position.
MS41-6153— Proportional, 0 to 10 Vdc or 2 to 10 Vdc selectable.
Power Requirements All 24 Vac circuits are Class 2.
Connections 3 ft. (0.9 m) long plenum-rated cable, 18 AWG color coded leads.
Motor Type Brushless motor technology with stall protection.
Outputs
Electrical Position feedback voltage for MS41-6153: 0 to 10 Vdc, 1 mA max.
Timing: Approx. 125 sec. at 60 Hz; 150 sec. at 50 Hz.
Mechanical Output torque rating: 133 lb-in (15 N-m).
Stroke: Angle of rotation is limited to a nominal 90° (maximum 95°), field adjustable
to limit travel on either end of stroke.
Position indicator: Adjustable pointer is provided for position indication.
Environment
Temperature Limits Shipping and storage: -40 to 158 °F (-40 to 70 °C) ambient.
Operating: -25 to 130 °F (32 to 55 °C)
Humidity 5 to 95% RH, non-condensing.
Locations NEMA 1 (IEC IP10).
Agency Listings (Actuator)
UL UL-873, Underwriters Laboratories.
European Community EMC Directive (89/336/EEC). Low Voltage Directive (72/23/EEC).
cUL Canadian Standards C22.2 No. 24-93.
Part Number
Power Input @ 50/60 Hz
Voltage
a
a
24 Vac, +20%, -5% (MF models) and 24 Vac, +20%, -10% (MS models) for ambient temperatures 85
to 130 °F.
Running VA Holding VA Watts
MF41-6153 24 Vac +20/-15% 3.0 — 3.0
MS41-6153 24 Vac +20/-15% 5.0 1.2 4.0