User Guide

2 © Copyright 2008 TAC All Rights Reserved. F-23576-6
SPECIFICATIONS
Actuator Inputs
Control Circuit:
MPR-561X and -563X Series, Two-wire.
MPR-571X and -573X Series, Three-wire.
Input Impedance: 82.5 Ω for 4 to 20 mA input.
Power Input: Refer to Table-1 and Table-2.
Connections: Color-coded 4' (1.2 m) leads.
Actuator Outputs
Electrical:
Position Signals, Internal feedback circuitry provides positive positioning of the damper
in relation to the controller signal.
Startpoint Adjustment, Adjustable potentiometer provides manual adjustment of the
actuator startpoint.
Mechanical:
Stroke,
Damper Approximately 2" (51 mm) from fully retracted to fully extended (includes
AM-601 linkage).
Valve Approximately 9/16" (14.3 mm) from fully retracted to fully extended.
Nominal Damper Area, Actuator sizing should be done in accordance with damper
manufacturer’s specifications.
Output Torque Rating, The proportional output torque rating of 15 lb-in. (1.7 N-m) is
available throughout the entire stroke and is based on the lowest force available under
normal operation, the spring return stroke, or at minimum (-10%) supply voltage.
Environment
Ambient Temperature Limits:
Shipping & Storage, -40 to 140° F (-40 to 60° C).
Operating,
Damper -20 to 140° F (-29 to 60° C).
Valve Refer to Table-3.
Humidity: 5 to 95% RH, non-condensing.
Location: NEMA Type 1, indoor only.
Agency Listings:
UL 873: Underwriters Laboratories (File # E9429 Category Temperature-Indicating and
Regulating Equipment).
CSA: Certified for use in Canada by Underwriters Laboratories. Canadian Standard
C22.2 No. 24-93.
European Community: EMC Directive (89/336/EEC). Low Voltage Directive
(72/23/EEC).