User Guide

F-23576-6 © Copyright 2008 TAC All Rights Reserved. 3
Table-1 Model Chart for Valve (Basic) Actuators.
Table-2 Model Chart for Damper Actuators.
Table-3 Restrictions on Maximum Ambient Temperature for Valve Actuators.
Part Number
a
Actuator Power Input
Timing in Seconds
@ 72° F (22° C)
Required Linkages
Input
Signal
AC
Voltage
+10/
-15%
Hz VA Watts
No Load Stroke Retract
on
Power
Loss
Valve
Applications
Damper
Applications
b
Extend Retract
MPR-5610 120
50/60 18 10 60 30 15
AV-600
AV-601
c
AM-601
Compatible
with
4 to 20 mA
MPR-5611 240
MPR-5613 24
MPR-5710
d
120 Compatible
with
135 ¾
Slidewire
(Series 90)
MPR-5711
d
240
MPR-5713 24
a
These MPR-5X1X series valve actuators are compatible with VB-7XXX 1/2" to 2" valve bodies.
b
The MPR-5X1X series actuators are basic models which may be equipped for damper applications with the installation of an AM-601 linkage.
c
May be required for steam and hot water. Refer to Table-3.
d
These actuators are obsolete. They are listed here for reference only.
Part Number
a
Actuator Power Input Timing in Seconds @ 72° F (22° C)
Input
Signal
AC
Voltage
+10/
-15%
Hz VA Watts
No Load Stroke
Retract on
Power
Loss
Extend Retract
MPR-5630 120
50 60 18 10 60 30 15
Compatible
with
4 to 20 mA
MPR-5633 24
MPR-5730
b
120 Compatible
with
135 ¾
Slidewire
(Series 90)
MPR-5733
b
24
a
Damper models (MPR-5X3X) are provided with factory-installed damper linkages. Only base models (MPR-5X1X) require separately-ordered linkages.
b
These actuators are obsolete. They are listed here for reference only.
Maximum Temperature of Media
in the Valve Body
(Check Rating of the Valve)
°F (°C)
Maximum Ambient Temperature
of MPR-563X and -573X Series
AV-600 (Only)
°F (°C)
AV-600 and AV-601
°F (°C)
366 (186)
Do Not Use
88 (31)
b
340 (171) 93 (34)
281 (138) 103 (39)
a
181 (83) 120 (48)
a
80 (26) 140 (60)
a
140 (60)
a
a
Maximum ambient temperature of the actuator must never exceed 140° F (60° C).