User Guide

3
Specifications,
Continued
Conformity
Product safety: Automatic electrical controls EN 60 730-2-14
for household and similar use (Type 1)
Electromagnetic compatibility (EMC) 89/336/EEC
Immunity for all models EN 61 000-6-2
Emissions for all models EN 50 081-1
Auxiliary features
Dual auxiliary switches
AC rating 24 Vac
AC 6A resistive,
AC 2A inductive
DC rating 12 to 30 Vdc
DC 2A
Switch Range
Switch A 0° to 90° with 5° intervals
Recommended range usage 0° to 45°
Factory setting
Switch B 0° to 90° with 5° intervals
Recommended range usage 45° to 90°
Factory setting 85°
Switching hysteresis
Miscellaneous
Pre-cabled connection 18 AWG
Cable length 3 feet (0.9 m) length
Life cycle Five-year warranty
Dimensions: Inches (mm) 8-3/8 H × 3-1/4 W × 2-2/3 D
(212 H × 83 W × 68 D)
Weight 2.2 lb (1 kg)
Actuator
Components
EA0957R1
14
15
EA0956R1
12
11
2
3
4
5
6
1
10
9
13
8
7
Figure 1. TAC DuraDrive Actuator
Components.
Legend
1. Actuator housing
2. Positioning scale for angle
of rotation
3. DIP switches and cover
4. Span adjustment
5. Offset (start point)
adjustment
6. Anti-rotation bracket
7. Connection cable for power
and control signals
8. Connection cable for
auxiliary switches
9. Manual override
10. Auxiliary switches A & B
11. Position indicator
12. Self centering shaft adapter
13. 1/2-inch NPT conduit
connection
14. Shaft adapter locking clip
15. Position indicator adapter